EasyManua.ls Logo

Carrier 38AK024-044 - Charge System

Carrier 38AK024-044
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
START-UP
Initial
Check
À
CAUTION
Do
not
attempt
to
start
the
condensing
unit,
even
mo-
mentarily,
until
the
following
steps
have
been
com-
pleted.
Compressor
damage
may
result.
1.
Check
all
auxiliary
components
such
as
air
handling
equipment,
and
other
equipment.
Consult
the
manu-
facturer's
instructions
regarding
any
other
equipment
connected
to
the
condensing
unit.
If
used,
air
flow
switch
must
be
properly
installed.
See
Fig.
9.
2.
Backseat
(open)
compressor
suction
and
discharge
valves.
Close
valves
one
turn
to
allow
pressure
to
reach
test
gages.
.
Open
liquid
line
service
valve.
.
Set
thermostat.
.
Check
tightness
of
all
electrical
connections.
.
Compressor
oil
level
should
be
visible
in
sightglass.
See
Service,
Oil
Charge.
7.
Be
sure
unit
is
properly
leak
checked,
dehydrated
and
charged.
See
below.
8.
Electrical
power
source
must
agree
with
nameplate
rating.
9.
Crankcase
heater
must
be
firmly
locked
into
compres-
sor
crankcase.
Be
sure
crankcase
is
warm
(heater
should
be
on
for
24
hours
before
starting
compressor).
10.
Be
sure
compressor
floats
freely
on
the
mounting
springs.
See
Compressor
Mounting
and
Fig.
3
for
loosening
compressor
bolts.
ON
Q
RU
Leak
Test
and
Dehydration
Leak
test
the
entire
refrigerant
system
by
the
pressure
method
described
in
the
Carrier
Service
Techniques
Manual,
Chapter
1,
Section
1-6.
Use
R-22
at
approximately
25
psig
backed
up
with
an
inert
gas
to
a total
pressure
not
to
exceed
200
psig.
Preliminary
Charge
Refer
to
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Section
1-8
for
charging
methods
and
procedures.
Charge
system
with
approximately
25
Ibs
of
R-22
by
the
liquid
charging
method
and
charging
by
weight
procedure.
Start
Unit
Close
field
disconnect,
fan
circuit
breaker
and
set
thermostat
above
ambient
temperature
so
that
there
is
no
demand
for
cooling.
Now,
only
the
crankcase
heater
is
energized.
After
the
heater
has
been
on
for
24
hours,
the
unit
can
be
started.
If
no
time
has
elapsed
since
the
preliminary
charge
step
has
been
completed,
it
is
unnecessary
to
wait
the
24-hour
period.
Close
the
compressor
circuit
breaker,
then
reset
the
indoor
thermostat
below
ambient
temperature,
so
that
a
call
for
cooling
is
ensured.
NOTE:
Do
not
use
the
compressor
circuit
breaker
to
start
and
stop
compressor,
except
in
an
emergency.
Depending
on
the
position
of
the
Time
Guard
timer,
start-up
of
the
compressor
occurs
within
12
seconds
and
8
minutes
from
the
time
the
control
circuit
is
energized.
Charge
System
Actual
start-up
should
be
done
only
under
supervision
of
a
qualified
refrigeration
mechanic.
Refer
to
charging
charts.
See
Fig.
10
through
13
for
the
particular
unit
being
charged.
Measure
pressure
at
the
liquid
line
service
valve,
being
sure
a
Schrader
depressure
is
used
if
required.
Also,
measure
liquid
line
temperature
as
close
to
the
liquid
service
valve
as
possible.
Add
charge
until
the
pressure
and
temperature
conditions
of
the
charging
chart
curve
are
met.
If
liquid
pressure
and
temperature
point
fall
below
curve,
add
charge.
If
liquid
pressure
and
temperature
point
fall
below
curve,
reduce
the
charge
until
the
conditions
match
the
curve.
A
CAUTION
Never
charge
liquid
into
the
low-pressure
side
of
system.
Do
not
overcharge.
During
charging
or
removal
of
refrigerant,
be
sure
indoor
fan
system
is
operating.
Operation
Refer
to
control
circuit
diagram
on
the
unit,
or
in
the
unit
wiring
book.

Related product manuals