Fig. 6 — Dimensional Drawing, 38AKS028,034
LEGEND
NEC — National Electrical Code
VAV — Variable Air Volume
NOTES:
1. There must be minimum (2440 mm) 8 ft. clear air space above
unit.
2. The approximate operating weight of the unit is:
50 AND 60 HZ
UNIT
WT
(Lb)
WT
(Kg)
38AKS028 1650 748
38AKS028C 1804 818
38AKS034 1803 818
38AKS034C 2009 911
3. A ‘‘C’’ in the model number indicates unit has factory-installed
copper coil.
8