132
0
1
2
3
4
5
6
7
40 50 60 70 80 90 100
RM.F=55.0 °F
Remote - Full Reset Temp
RM.NO=85.0 °F
Remote - No Reset Temp
RM.DG=6.0 ΔF
Remote Degrees Reset
TEMPERATURE RESET APPLIED TO ACTIVE SETPOINT, °F
OUTSIDE AIR TEMPERATURE, °F
A38-7302
Fig. 151 — Outside Air Temperature Reset, °F (CRST=2)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
5.0 10.0 15.0 20.0 25.0 30.0 35.0
RM.F=12.8 °C
Remote - Full Reset Temp
RM.NO=29.4 °C
Remote - No Reset Temp
RM.DG=3.3 ΔC
Remote Degrees Reset
OUTSIDE AIR TEMPERATURE, °C
TEMPERATURE RESET APPLIED TO ACTIVE SETPOINT, °C
A38-7303
Fig. 152 — Outside Air Temperature Reset, °C (CRST=2)