APPENDIX A — DISPLAY TABLES (cont)
Run Status Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
VIEW
AUTO VIEW OF RUN STATUS
RAT XXX.X °F (°C) Return Air Temperature
SAT XXX.X °F (°C) Supply Air Temperature
SETP XXX.X °F (°C) Active Set Point
CTPT XXX.X °F (°C) Control Point
LOD.F XXX Load/Unload Factor
STAT X Control Mode
Range: 1 to 9
1=Off Local
2=Off CCN
3=Off Time
4=Off Emrgcy
5=On Local
6=On CCN
7=On Time
8=IDFS Not On
9=SPT Satisfied
SPT.M X Space Temp Control Mode
Range: 0 to 3
0=COOL OFF
1=LO COOL
2=HI COOL
3=COOL ON
OCC YES/NO Occupied
MODE YES/NO Override Modes in Effect
CAP XXX% Percent Total Capacity
STGE X Requested Stage
ALRM XXX Current Alarms & Alerts
TIME HH:MM Time of Day 00:00-23:59
MNTH XX Month of Year
Range: 1 to 12
1=January
2=February
etc.
DATE XX Day of Month Range: 1 to 31
YEAR XXXX Year of Century
RUN
UNIT RUN HOUR AND START
HRS.U XXXX HRS Machine Operating Hours
STR.U XXXX Machine Starts
HOUR
CIRC AND COMP RUN HOURS
HRS.A XXXX HRS Circuit A Run Hours
HRS.B XXXX HRS Circuit B Run Hours
HR.A1 XXXX HRS Compressor A1 Run Hours
HR.A2 XXXX HRS Compressor A2 Run Hours
HR.A3 XXXX HRS Compressor A3 Run Hours
HR.B1 XXXX HRS Compressor B1 Run Hours
HR.B2 XXXX HRS Compressor B2 Run Hours
HR.B3 XXXX HRS Compressor B3 Run Hours