131
Outside Air Temperature Reset
— The 38AP units are
shipped with an outside air sensor, so no additional sensors are
required.
To use Outside Air Temperature Reset, four variables must
be configured. In Configuration
RSET, set these items:
• Cooling Reset Type (CRST): Configure for the type of
reset desired, Outside Air Temperature
• Remote – No Reset Temp (RM.NO): Set to the tempera-
ture that no reset should occur
• Remote – Full Reset Temp (RM.F): Set to the tempera-
ture that maximum reset is to occur
• Remote – Degrees Reset (RM.DG): Set to the maximum
amount of reset desired
The Outside Air Temperature Reset example shown in Table
60 and Fig. 151 and 152 provides 0° F (0° C) reset to the
Active Set Point (Run Status
VIEW
SETP) if Outside Air
Temperature (Tem pera tures
UNIT
OAT)=85 F (29.4 C)
and 6 F (3.3 C) reset if OAT=55 F (12.8 C). Using these val-
ues, if SETP=55 F (12.8 C) and OAT=55 F (12.8 C) or less,
the Control Point (Run Status
VIEW
CTPT) will reflect
6° F (3.3° C) reset or 61 F (16.1 C). If OAT=85 F (29.4 C) or
more, the control point Run Status
VIEW
CTPT will
reflect 0° F (0.0° C) reset or 55 F (12.8 C). Between
OAT=55 F (12.8 C) and OAT=85 F (29.4 C) a proportional
reset amount will be applied to CTPT.
Table 60 — Configuring Outside Air Temperature Reset
*Not supported.
CONFIGURATION
OPT2
ITEM EXPANSION COMMENTS EXAMPLE VALUE
C.TYP Machine Control Type
Range: 1 to 9
1 (VAV)
3 (Tstat Multi)
4 (Tstat 2stg)
5 (SPT Multi)
7 (PCT Cap)
8 (Dual Tstat)
9 (VAV Setpoint)
Default: 4
Value must be set to 1, 3, 5 or 9
1, 3, 5 or 9
CONFIGURATION
RSET
CRST Cooling Reset Type
0=No Reset (Default)
1=4-20 Input
2=Out Air Temp
3=Return*
4=Space Temp
2
RM.NO Remote – No Reset Temp
Range: 0.0 to 125.0 F
(–17.8 to 51.7 C)
Default: 125.0 F (51.7 C)
85.0 F (29.4 C)
RM.F Remote – Full Reset Temp
Range: 0.0 to 125.0 F
(–17.8 to 51.7 C)
Default: 0.0 F (–17.8 C)
55.0 F (12.8 C)
RM.DG Remote – Degrees Reset
Range: –30.0 to 30.0 'F
(–16.7 to 16.7 'C)
Default: 0.0 'F (0.0 'C)
6.0 'F
(3.3 'C)