196
APPENDIX B — CCN TABLES (cont)
Status Tables (cont)
CIRCADIO (Circuit A Discrete Inputs/Outputs)
CIRCB_AN (Circuit B Analog Parameters)
CIRCBDIO (Circuit B Discrete Inputs/Outputs)
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
CIRC.A DISCRETE OUTPUTS
Compressor A1 Relay OFF/ON K_A1_RLY Read Only
Comp A1 Load Percent NNN.n % DIGITAL% Read Only
Compressor A2 Relay OFF/ON K_A2_RLY Read Only
Compressor A3 Relay OFF/ON K_A3_RLY Read Only
Minimum Load Valve Relay OFF/ON MLV_RLY Read Only
Liquid Line Solenoid A OFF/ON LLSV_A Read Only
Liquid Line Solenoid A2 OFF/ON LLSV_A2 Read Only
CIRC.A DISCRETE INPUTS
Compressor A1 Feedback OFF/ON K_A1_FBK Read Only
Compressor A2 Feedback OFF/ON K_A2_FBK Read Only
Compressor A3 Feedback OFF/ON K_A3_FBK Read Only
High Pressure Switch A OPEN/CLOSE HPSA Read Only
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
CIRC.B ANALOG VALUES
Percent Total Capacity NNN % CAPB_T Read Only
Percent Available Cap. NNN % CAPB_A Read Only
Discharge Pressure NNN.n psig (kPa) DP_B Read Only
Suction Pressure NNN.n psig (kPa) SP_B Read Only
Saturated Condensing Tmp NNN.n °F (°C) SCTB Read Only
Saturated Suction Temp NNN.n °F (°C) SSTB Read Only
Var Head Press Out Cir B NNN.n % VHPB_ACT Read Only
Compr Return Gas Temp NNN.n °F (°C) RGTB Read Only
Suction Superheat Temp NNN.n 'F ('C) SH_B Read Only
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
CIRC.B DISCRETE OUTPUTS
Compressor B1 Relay OFF/ON K_B1_RLY Read Only
Compressor B2 Relay OFF/ON K_B2_RLY Read Only
Compressor B3 Relay OFF/ON K_B3_RLY Read Only
Minimum Load Valve Relay OFF/ON MLV_RLY Read Only
Liquid Line Solenoid B OFF/ON LLSV_B Read Only
Liquid Line Solenoid B2 OFF/ON LLSV_B2 Read Only
CIRC.B DISCRETE INPUTS
Compressor B1 Feedback OFF/ON K_B1_FBK Read Only
Compressor B2 Feedback OFF/ON K_B2_FBK Read Only
Compressor B3 Feedback OFF/ON K_B3_FBK Read Only
High Pressure Switch B OPEN/CLOSE HPSB Read Only