203
APPENDIX B — CCN TABLES (cont)
Configuration Tables (cont)
HPB (Head Pressure Circuit B)
OPTIONS1 (Options 1 Configuration)
*Based on unit model. If the unit is equipped with the option, the
default is Yes, otherwise, No.
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
SCT Delta for Comp B1 NNN.n 'F ('C) B1SCTDT Configuration
SCT Delta for Comp B2 NNN.n 'F ('C) B2SCTDT Configuration
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
Motormaster Select
No/Yes
Default: No/Yes*
MM_SLCT Configuration
Minimum Load Vlv Select
No/Yes
Default: No
MLV_FLG Configuration
CSB Boards Enable
Disable/Enable
Default: Enable
CSB_ENA Configuration
Space Temp Sensor
Disable/Enable
Default: Disable
SPTSENS Configuration
Space Temp Offset Enable
Disable/Enable
Default: Disable
SPTOSENS Configuration
Space Temp Offset Range
NN
Range: 1 to 10 (0.6 to 5.6)
Default: 5 (2.8)
'F ('C) SPTO_RNG Configuration
RAT Thermistor Type
N
Range:
0 = 5k
1 = 10k
2 = None
Default: 1
RATTYPE Configuration
SAT Thermistor Type
N
Range:
0 = 5k
1 = 10k
2 = None
Default: 1
SATTYPE Configuration
EMM Module installed
No/Yes
Default: No/Yes*
EMM_BRD Configuration