218
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Temperature Reset MODE_14 R ON_OFF BV:40 mode_14_1
Time Guard Active MODE_TG R ON_OFF BV:67 mode_tg_1
Timed Override in effect MODE_6 R ON_OFF BV:34 mode_6_1
User Defined Analog 1 R/W AV:2901 user_analog_1_1
User Defined Analog 2 R/W AV:2902 user_analog_2_1
User Defined Analog 3 R/W AV:2903 user_analog_3_1
User Defined Analog 4 R/W AV:2904 user_analog_4_1
User Defined Analog 5 R/W AV:2905 user_analog_5_1
User Defined Binary 1 R/W ON_OFF BV:2911 user_binary_1_1
User Defined Binary 2 R/W ON_OFF BV:2912 user_binary_2_1
User Defined Binary 3 R/W ON_OFF BV:2913 user_binary_3_1
User Defined Binary 4 R/W ON_OFF BV:2914 user_binary_4_1
User Defined Binary 5 R/W ON_OFF BV:2915 user_binary_5_1
Var Head Press Output
Circuit A
VHPA_ACT R % 0-100 AV:19 vhpa_act_1
Var Head Press Output
Circuit B
VHPB_ACT R % 0-100 AV:83 vhpb_act_1
Y1 Thermostat Input Y1 R ON_OFF BV:27 y1_1
Y2 Thermostat Input Y2 R ON_OFF BV:28 y2_1
Y3 Thermostat Input Y3 R ON_OFF BV:29 y3_1
Y4 Thermostat Input Y4 R ON_OFF BV:30 y4_1
R—Read
W—Write