18
NOMINAL CAPACITIES
NOTES:
1. Gross cooling capacity is based on 67 F wb, 80 F db air entering indoor unit and 95 F db air enter-
ing outdoor unit.
2. Net heating capacity is based on 70 F db air entering indoor unit and 47 F db, 43 F wb air entering
outdoor unit. Includes indoor fan heat and defrost effects.
INTEGRATED HEATING CAPACITIES
LEGEND
NOTES:
1. To obtain total outdoor unit power, add outdoor fan kW shown to compressor draw:
38AQS008 .96 kW; 38AQS012 and 016 1.4 kW.
2. Ratings are without supplementary heat and are based on 70 F db air entering indoor unit.
Wet-bulb temperature entering outdoor unit varies with dry bulb; at 47 F db, wb is 43 F; at
17 F db, wb is 15 F.
OUTDOOR UNIT
38AQS
INDOOR UNIT
40RMQ
AIRFLOW
(Cfm)
GROSS COOLING
CAPACITY (Btuh)
NET HEATING
CAPACITY (Btuh)
008 008
3000 89,000 83,000
012 012
4000 113,000 111,000
016 016
6000 179,000 164,000
OUTDOOR
UNIT
38AQS
INDOOR
UNIT
40RMQ
AIRFLOW
(Cfm)
TEMPERATURE OF AIR ENTERING OUTDOOR UNIT (F db)
100 101720
Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW
008 008
3000 21.7 3.4 30.4 3.8 39.4 4.3 45.8 4.6 48.3 4.8
012 012
4000 33.3 4.2 43.4 4.8 54.2 5.4 61.8 5.8 65.1 6.0
016 016
6000 54.1 7.2 68.3 8.0 83.2 8.8 93.8 9.4 98.9 9.7
OUTDOOR
UNIT
38AQS
INDOOR
UNIT
40RMQ
AIRFLOW
(Cfm)
TEMPERATURE OF AIR ENTERING OUTDOOR UNIT (F db)
30 40 47 50 60
Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW
008 008
3000 56.2 5.3 75.9 5.9 83.4 6.3 86.8 6.5 98.4 7.1
012 012
4000 74.5 6.7 100.0 7.5 111.0 8.1 116.0 8.4 132.0 9.2
016 016
6000 112.0 10.6 149.0 11.7 163.0 12.3 171.0 12.7 194.0 13.7
Cap.
Integrated Heating Capacity (1000 Btuh) includes
indoor-fan motor heat and effects of defrost.
kW
Total Compressor Motor Power Input
Performance data