25
OUTDOOR UNITS
LEGEND
INDOOR UNITS — STANDARD MOTORS
LEGEND
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.
INDOOR UNITS — ALTERNATE MOTORS
LEGEND
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.
UNIT
38AQS
V-PH-Hz
VOLTAGE RANGE COMPR FAN MOTORS POWER SUPPLY
Min Max LRA RLA
No. of
Fans
FLA
Min Ckt
Amps
MOCP
(Amps)
Fan No. 1 Fan No. 2
008
208/230-3-60 187 254 160 31.5 1 3.1 42.5 50
460-3-60 414 508 80 15.7 1 1.4 21.0 25
012
208/230-3-60 187 253 170 43.6 2 4.3 3.7 62.5 100
460-3-60 414 528 77 20.0 2 2.3 1.9 29.1 40
575-3-60 518 660 62 15.7 2 1.8 1.8 22.8 35
016
208/230-3-60 187 253 266 63.6 2 4.3 3.7 87.5 125
460-3-60 414 528 120 29.3 2 2.3 1.9 40.7 60
575-3-60 518 660 96 23.8 2 1.8 1.8 33.0 50
FLA
Full Load Amps
LRA
Locked Rotor Amps
MOCP
Maximum Overcurrent Protection (Fuse Only)
RLA
Rated Load Amps
UNIT
40RMQ
V*-PH-Hz
VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp FLA
Minimum
Circuit
Amps
MOCP
(Amps)
008
208/230-1-60 187-253 2.4 11.0 13.8 20
208/230-3-60 187-253 2.4 5.2 6.5 15
460-3-60 414-506 2.4 2.6 3.3 15
575-3-60 518-632 2.0 2.3 2.9 15
012
208/230-3-60 187-253 2.4 5.2 6.5 15
460-3-60 414-506 2.4 2.6 3.3 15
575-3-60 518-632 2.0 2.3 2.9 15
016
208/230-3-60 187-253 3.7 10.2 12.8 20
460-3-60 414-506 3.7 4.8 6.0 15
575-3-60 518-632 3.0 3.8 4.8 15
FLA
Full Load Amps
Hp
Horsepower
MOCP
Maximum Overcurrent Protection
UNIT
40RMQ
V*-PH-Hz
VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp FLA
Minimum
Circuit
Amps
MOCP
(Amps)
008
208/230-1-60 187-253 2.4 11.0 13.8 20
208/230-3-60 187-253 2.9 7.5 9.4 15
460-3-60 414-506 2.9 3.4 4.3 15
575-3-60 518-632 3.0 3.8 4.8 15
012
208/230-3-60 187-253 3.7 10.2 12.8 20
460-3-60 414-506 3.7 4.8 6.0 15
575-3-60 518-632 3.0 3.8 4.8 15
016
208/230-3-60 187-253 5.0 15.3/12.8 19.1/16.0 30/25
460-3-60 414-506 5.0 6.4 8.0 15
575-3-60 518-632 5.0 5.1 6.4 15
FLA
Full Load Amps
Hp
Horsepower
MOCP
Maximum Overcurrent Protection