EasyManua.ls Logo

Carrier 38AUD 16 Series - Preliminary Charge; Step 6 - Install Accessories

Carrier 38AUD 16 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Step 6 Complete Refrigerant Piping Connections
IMPORTANT: Do not bury refrige rant piping
underground.
IMPORTANT: A refrigerant receiver is not provided
with the unit. Do not install a receiver.
Provide Safety Relief
If local codes dictate an additional safety relief device,
purchase locally and install locally. Installation will
require the recovery of the f actory shipping charge before
the factory tubing can be cut and the supplemental relief
device is installed.
Model 38AUD has two separate refrigeration systems. If
required, each circuit will require a field-supplied/installed
supplemental relief device.
Check 38AU Model with Evaporator Coil Connections
Confirm before installation of unit that the evaporator coil
connec tions are consistent with this 38AU model. See
Table 3 on page 11.
Insulate Suction Lines
Apply closed-cell tubular insulation to all suction lines
between evaporator coil connection and 38AU unit’ s suction
service valve.
38AUD Piping Connections
The 38AUD’ s two circuits are designated Circuit 1 and
Circuit 2. Circuit 1 is contro lled by the thermos tat’s Y1 (or
TC1) contact and will be the first circuit on and last circuit
off. Circuit 2 is controlled by the thermostat’ s Y2 (or TC2)
contact and this circuit is always the “lag” circuit.
See Fig . 8 for location of Circuit 1 and Circuit 2 service
valves and field piping connections. Circuit 1 is on the
left-han d side of the serv ice valve compar tment; Circuit 2 is
on the right.
When a sin g le piece evap or ator coil with two sep arate
circuits is connected to a 38AUD, the lower coil circuit
should be connected to the 38AUD’s Circuit 1 so that the
evaporators lower coil segment is first-on/last-off (to avoid
re-evaporation of condensate on dry lower coil segments).
Circuit 1
Connections
Circuit 2
Connections
CKT
1
CKT
1
CKT
2
CKT
2
C10355
Fig. 8 -- 38AUD Service Valve Loc ations
Plan the Circuit 1 and Circuit 2 tubing segments carefully,
mark each segment and check constantly as piping
systems are assembled to avoid piping errors.
38AUD unit cannot be field-piped as a
single-circuit/tandem system.
Final Tubing Check. 38AUD
Before completing the field piping connections to the
38AUD unit service valves, confirm that the suction line
to the indoor coils first--on/last--off circuit (and its
companion liquid line) are correctly identified as Circuit 1
use for the 38AUD unit. If a suction riser is required, it
must be in Circuit 1.
Connecting 40RU to 38AUD: The 40RU fan coil in sizes
16, 25 and 28 is a face-split coil des ign that also has its
circuits desig nated as 1 and 2. See F ig . 9. Note that th e
lower coil segment changes as the arrangement of the 40RU
changes. In a vertical arrangement, the 40RU’ s lower coil
segment is segment 2; this segment should be connected to
the 38AUD’ s Circuit 1. In a horizontal arrangement, the
40RU’s lower segment is now segment 1; this segment
should be connected to the 38AUD’ s Circuit 1.
Note that refrigerant suction piping should be insulated.
40RU
Arrangement
Cooling
Stage
40RU Coil
Segment
Connect to
38AUD
Vertical
Y1
Y2
2
1
Circuit 1
Circuit 2
Horizontal
Y1
Y2
1
2
Circuit 1
Circuit 2
FIRST ON/LAST OFF = 2
VERTICAL INSTALLATION
FIRST ON/LA ST OF F = 1
HORIZONTAL INSTALLATION
1
2
2
1
C10071
Fig. 9 -- Typical Evaporator Coil Connections (40RU)
38AU

Table of Contents

Related product manuals