Step 9 Wind Baffles for Low Ambient Control
38AUZE08 includes the factory installed 32LT Motormaster
Low A mbien t Con tro l.
Units with 32LT Motormaster control require the addition
of wind baffles to ensure full ra nge low ambient
operation. Material data and dimensions for wind baffles
are incl uded in the Appendix C section, Low Ambient
Control, starting on page 29. Fabricate the wind baffles
and mount per instructions.
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or
Star t-U p , review S tart- U p Checklis t at the back of this
book. The Checklist assures proper start-up of a unit
and provides a record of unit condition, application
requirements, system information, and operation at
initial start- up .
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
dama ge.
Do not attempt to start the condensing unit, even
momentarily, until the following steps have been
completed. Compressor damage may result.
CAUTION
!
System Check
1. The electrical power source must agree with the unit’s
name plate rating.
2. Check all air handl er( s ) and other equipment auxiliary
components. Consult the manufacturer s instructions re-
garding any other equipment connected to the condens-
ing unit. If the unit has field-ins talled access or ies , be
sure all are properly installed and correctly wired. If
used, the airflow switch must be properly installed.
3. Check tightness of all electrical connections.
4. Be sure liquid line and low side of the system are
properly leak checked and dehydrat ed.
5. Be sure the unit is properly charged. See “Preliminary
Charge”, below.
6. Open the liquid line and suction line service valves.
7. The crankcase heater must be firmly attached to the
compressor crankcase. Be sure the crankcase is warm
(heater must be on for 24 hours before starting
compressor).
Turn On Crankcase Heater
Turn on the crankcase heater for 24 hours before starting
the unit to be sure all the refrigerant is out of the oil.To
energize the crankcase heater, proceed as follows:
1. Set the space thermostat set point above the space
temperature so there is no demand for cooling.
2. Close the field disconnect.
Preliminary Charge
Befor e starting the unit, charge liquid refrigerant into the
high side of the system through the liquid service valve. The
amount of refrigerant added must be at least 80% of the
operating char ge listed in the Physical Data table (T ables 1
and 2 on page 5). Allow high and low sid e press ur es to
equalize before starting compressor . If press ures do not
equalize readily, charge vapor on low side of system to
assure char ge in the evaporator . Refer to GTAC II, Module
5, Char ging, Recover , Recycling, and Reclamation for liquid
charging procedures.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
dama ge.
Prior to starting compressor, a preliminary charge of
refrigerant must be added to avoid possible
compressor damage.
CAUTION
!
START-UP
38AU Units: The c ompressor crankc ase heater must be on
for 24 hours be fore start-up. After the heater has been on
for 24 hours, the unit can be started. If no time elapsed
since the preliminary charge step was completed, it is
unnece ssary to wait the 24-hour period.
Preliminary Checks
1. Check that electric power supply agrees with unit
nameplate data.
2. Verify that the compressor crankcase heater is se-
curely in place.
3. Check that the compressor crankcase heater has been
on at least 24 hours.
4. Recheck for leaks using the procedure outlined in the
Pre-Start-Up sec tion, Lea k Test and Dehydration. If
any leaks are detected, repair as required. Evacuate
and dehydrate as describe d in the Leak Test and De-
hydration section.
5. Ensure that the preliminary charge has been added as
described in the Pre-Start-Up section, Preliminary
Charge.
6. All inte rnal wiring connections must be tight , and all
barriers and covers must be in place.
NOTE: The 38AU units are factory charged with the
required amount of oil. If recharging in required, use
Emkarate RL 32-3MAF for the 38AU units.
Compressor Rotation
On 3--phase units with scroll compres s o rs , it is importan t to
be certain that the compressor is rotating in the proper
direction. 38AU units are equipped with a Comfort Alert
Diagnostic Module (CADM). Alert Code 7 indicates reverse
power phasing.
38AU