16
Detailed cooling capacities* continued
See notes on pg. 21.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
38BRC030-31 Outdoor Section With CC5A/CD5AA030 Indoor Section
875
72
67
62
57
32.3
29.5
26.9
25.5
15.8
19.8
23.8
25.5
2.41
2.39
2.37
2.36
31.2
28.5
25.9
24.7
15.4
19.4
23.3
24.7
2.65
2.62
2.61
2.60
30.0
27.4
24.9
23.9
14.9
18.9
22.8
23.9
2.91
2.88
2.87
2.86
28.8
26.2
23.8
23.1
14.5
18.5
22.3
23.1
3.21
3.18
3.15
3.16
27.5
25.1
22.8
22.3
14.0
18.0
21.7
22.3
3.54
3.52
3.47
3.50
1000
72
67
62
57
32.9
30.1
27.4
26.5
16.4
21.0
25.3
26.5
2.46
2.44
2.42
2.42
31.7
29.0
26.4
25.6
16.0
20.5
24.8
25.6
2.70
2.67
2.66
2.65
30.5
27.9
25.3
24.8
15.6
20.1
24.2
24.8
2.96
2.94
2.91
2.91
29.2
26.7
24.3
24.0
15.1
19.6
23.6
24.0
3.26
3.23
3.18
3.21
28.0
25.5
23.3
23.1
14.6
19.1
23.0
23.1
3.59
3.57
3.55
3.55
1125
72
67
62
57
33.4
30.6
27.9
27.3
17.1
22.1
26.7
27.3
2.51
2.49
2.47
2.47
32.2
29.4
26.8
26.4
16.6
21.7
26.1
26.4
2.75
2.73
2.71
2.70
30.9
28.2
25.8
25.6
16.2
21.2
25.4
25.6
3.01
2.99
2.96
2.96
29.6
27.0
24.7
24.7
15.7
20.7
24.7
24.7
3.31
3.28
3.26
3.26
28.3
25.7
23.8
23.8
15.2
20.2
23.8
23.8
3.65
3.58
3.58
3.60
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
CC5A/CD5AA 030 1.00 1.00 CC5A/CD5AW 030 1.00 0.96
036 1.02 1.00 CD5AW 036 1.02 0.95
CC5A/CD5AW 030 1.00 1.00 CK3BA 030 1.00 0.96
CD5AW 036 1.02 1.00 036 1.02 0.94
CE3AA 030 1.00 1.00 CK5A/CK5BW 030 1.00 0.96
036 1.02 1.00 036 1.02 0.94
CF5AA 036 1.02 1.00
COILS + 58MVP080-20 VARIABLE-SPEED FURNACE
CK3BA 030 1.00 1.00 CK3BA 030 1.00 0.97
036 1.02 1.00 036 1.02 0.95
CK5A/CK5BA 030 1.00 1.00 CK5A/CK5BW 030 1.00 0.97
036 1.02 1.00 036 1.02 0.95
CK5A/CK5BN 036 0.95 1.00
COILS + 58MVP100-20 VARIABLE-SPEED FURNACE
CK5A/CK5BW 030 1.00 1.00 CK3BA 030 1.00 0.94
036 1.02 1.00 036 1.02 0.93
F(A,B)4AN(F,C) 030 1.01 0.99 CK5A/CK5BW 030 1.00 0.94
036 1.02 1.01 036 1.02 0.93
FC4BNF 030 1.01 0.99
COILS + 58MVP120-20 VARIABLE-SPEED FURNACE
036 1.02 1.01 CK3BA 030 1.00 0.95
FF1(B,C,D)NA 030 1.00 1.00 036 1.02 0.93
FG3AAA 036 1.02 1.00 CK5A/CK5BW 036 1.02 0.93
FK4CNF 001 1.01 0.93
COILS + 58U(H,X)V060-12 VARIABLE-SPEED FURNACE
40FKA/FK4CNF 002 1.01 0.93 CC5A/CD5AA 030 1.00 0.94
003 1.03 0.91 036 1.02 0.93
005 1.03 0.90 CC5A/CD5AW 030 1.00 0.94
COILS + 58MVP040-14 VARIABLE-SPEED FURNACE CD5AW 036 1.02 0.93
CC5A/CD5AA 030 1.00 0.96 CE3AA 030 1.00 0.94
036 1.02 0.95 036 1.02 0.94
CC5A/CD5AW 030 1.00 0.96 CK3BA 030 1.00 0.94
CD5AW 036 1.02 0.95 036 1.02 0.92
CK3BA 030 1.00 0.97 CK5A/CK5BA 030 1.00 0.94
036 1.02 0.95 036 1.02 0.92
CK5A/CK5BW 030 1.00 0.97 CK5A/CK5BN 036 0.95 0.93
036 1.02 0.95 CK5A/CK5BW 030 1.00 0.94
COILS + 58MVP060-14 VARIABLE-SPEED FURNACE COILS + 58U(H,X)V080-16 VARIABLE-SPEED FURNACE
CC5A/CD5AA 030 1.00 0.96 CC5A/CD5AA 030 1.00 0.94
036 1.02 0.95 036 1.02 0.93
CC5A/CD5AW 030 1.00 0.96 CC5A/CD5AW 030 1.00 0.94
CD5AW 036 1.02 0.95 CD5AW 036 1.02 0.93
CK3BA 030 1.00 0.96 CE3AA 030 1.00 0.94
036 1.02 0.95 036 1.02 0.94
CK5A/CK5BA 036 1.02 0.95 CK3BA 030 1.00 0.93
CK5A/CK5BW 030 1.00 0.96 036 1.02 0.91
COILS + 58MVP080-14 VARIABLE-SPEED FURNACE CK5A/CK5BW 030 1.00 0.93
CC5A/CD5AA 030 1.00 0.96 036 1.02 0.91
036 1.02 0.95 —— —