19
Detailed cooling capacities* continued
See notes on pg. 21.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85 95 105 115 125
CFM EWB
Capacity
MBtuh
Total
System
KW**
Capacity
MBtuh
Total
System
KW**
Capacity
MBtuh
Total
System
KW**
Capacity
MBtuh
Total
System
KW**
Capacity
MBtuh
Total
System
KW**Total Sens Total Sens Total Sens Total Sens Total Sens
38BRC042-32, 33, 52, 53 Outdoor Section With CC5A/CD5AA042 Indoor Section
1225
72
67
62
57
44.8
41.1
37.5
35.9
22.1
28.1
33.8
35.9
3.42
3.38
3.33
3.32
42.9
39.4
36.0
34.8
21.4
27.4
33.1
34.8
3.75
3.71
3.67
3.66
41.1
37.7
34.4
33.5
20.8
26.7
32.2
33.5
4.13
4.09
4.02
4.01
39.1
35.8
32.8
32.0
20.0
25.9
31.4
32.0
4.53
4.48
4.42
4.40
36.8
33.8
31.0
30.7
19.2
25.1
30.3
30.7
4.96
4.89
4.83
4.83
1400
72
67
62
57
45.5
41.8
38.3
37.2
23.1
29.8
36.0
37.2
3.49
3.45
3.41
3.39
43.7
40.0
36.7
36.0
22.5
29.0
35.1
36.0
3.84
3.77
3.73
3.73
41.7
38.3
35.1
34.7
21.7
28.4
34.3
34.7
4.20
4.15
4.11
4.11
39.5
36.3
33.4
33.2
21.0
27.6
33.1
33.2
4.60
4.55
4.49
4.50
37.2
34.1
31.6
31.8
20.1
26.7
31.6
31.8
5.03
4.96
4.90
4.93
1575
72
67
62
57
45.9
42.3
38.9
38.4
24.0
31.4
37.9
38.4
3.56
3.51
3.47
3.48
44.1
40.6
37.3
37.0
23.3
30.7
36.9
37.0
3.90
3.86
3.80
3.80
42.1
38.7
35.7
35.7
22.6
29.9
35.7
35.7
4.27
4.22
4.17
4.18
39.8
36.6
34.1
34.2
21.8
29.1
34.1
34.2
4.67
4.61
4.57
4.59
37.4
34.4
32.5
32.6
21.0
28.2
32.5
32.6
5.10
5.03
5.01
5.01
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
CC5A/CD5AA 042 1.00 1.00 CC5A/CD5AW 042 1.00 0.93
CC5A/CD5AC 048 1.00 0.99 048 1.00 0.93
CC5A/CD5AW 042 1.00 1.00 CD5AA 048 1.00 0.93
048 1.01 1.00 CK3BA 048 1.01 0.93
CD5AA 048 1.01 1.00 CK5A/CK5BA 048 1.01 0.97
CE3AA 042 1.00 1.00 CK5A/CK5BT 048 1.01 0.93
048 1.01 1.00
COILS + 58MVP120-20 VARIABLE-SPEED FURNACE
CF5AA 048 1.01 1.00 CK5A/CK5BW 048 1.01 0.93
CK3BA 042 1.00 1.00
COILS + 58U(H,X)V080-16 VARIABLE-SPEED FURNACE
048 1.01 1.00 CC5A/CD5AA 042 1.00 0.94
CK5A/CK5BA 042 1.00 1.00 CC5A/CD5AW 042 1.00 0.94
048 1.01 1.00 048 1.01 0.93
CK5A/CK5BN 042 0.98 1.00 CD5AA 048 1.01 0.93
048 0.99 1.00 CE3AA 042 1.00 0.94
CK5A/CK5BT 042 1.00 1.00 048 1.01 0.94
048 1.01 1.00 CK3BA 042 1.00 0.94
CK5A/CK5BW 048 1.01 1.00 048 1.01 0.94
F(A,B)4AN(F,B,C) 042 1.00 1.01 CK5A/CK5BA 042 1.00 0.94
048 1.01 1.02 048 1.01 0.94
FC4BN(F,B) 042 1.00 1.01 CK5A/CK5BT 042 1.00 0.94
048 1.01 1.02 048 1.01 0.94
FC4BNB 054 1.05 0.99
COILS + 58U(H,X)V100-20 VARIABLE-SPEED FURNACE
FG3AAA 048 1.01 1.00 CC5A/CD5AW 042 1.00 0.92
FK4CNB 006 1.05 0.92 048 1.01 0.92
FK4CNF 003 1.03 0.93 CD5AA 048 1.01 0.92
005 1.04 0.93 CE3AA 042 1.00 0.93
COILS + 58MVP080-14 VARIABLE-SPEED FURNACE 048 1.01 0.93
CC5A/CD5AA 042 1.00 0.94 CK3BA 042 1.00 0.93
CC5A/CD5AW 042 1.00 0.94 CK5A/CK5BA 042 1.00 0.93
048 1.00 0.93 CK5A/CK5BT 042 1.00 0.93
CD5AA 048 1.00 0.93 CK5A/CK5BW 048 1.01 0.93
CK3BA 048 1.00 0.95
COILS + 58U(H,X)V120-20 VARIABLE-SPEED FURNACE
CK5A/CK5BA 048 1.00 0.95 CC5A/CD5AW 042 1.00 0.94
CK5A/CK5BT 048 1.00 0.95 048 1.01 0.93
COILS + 58MVP080-20 VARIABLE-SPEED FURNACE CD5AA 048 1.01 0.93
CK3BA 048 1.01 0.95 CE3AA 042 1.00 0.94
CK5A/CK5BA 048 1.01 0.95 048 1.01 0.94
CK5A/CK5BT 048 1.01 0.95 CK3BA 042 1.00 0.93
COILS + 58MVP100-20 VARIABLE-SPEED FURNACE CK5A/CK5BA 042 1.00 0.93
CC5A/CD5AA 042 1.00 0.94 CK5A/CK5BT 042 1.00 0.93
—— CK5A/CK5BW 048 1.01 0.92