EasyManua.ls Logo

Carrier 38E - AccuRater Bypass Component Service; Reversing Valve Operation and Testing

Carrier 38E
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
This
type
of
fitting
is
easily
repaired
if
leaks
develop.
A
CAUTION
Wear
safety
glasses
and
gloves
when
handling
refrigerants.
Frontseat
outdoor
section
service
valves
after
relieving
refrigerant
pressure
in
system.
Back
locknut
off
Carrier
Compatible
Fitting
onto
tube.
Cut
fitting
between
threads
and
O-ring.
Remove
tubing
section
remaining
in
threaded
portion
of
fitting.
Discard
locknut.
Clean,
flux
and
insert
new
tube
end
into
remaining
portion
of
Carrier
Compatible
Fitting.
Wrap
valve
in
wet
cloth
to
prevent
damaging
valve.
Heat
and
apply
low-
temperature
solder
(430
F
[221
C]).
Leaking
Sweat
Connection
Frontseat
service
valves
and
relieve
refrigerant
pressure
in
tubing.
Clean
and
flux
area
around
leak
and
apply
low-temperature
solder
(430
F
[221
C]).
Liquid
line
service
valves
on
all
heat
pump
models
differ
from
condensing
unit
valves
in
that
heat
pump
connection
has
3/8-in.
male
flare.
When
making
connec¬
tion,
remove
flare
nut,
install
it
on
liquid
line
prior
to
flaring.
Flare
liquid
line
using
standard
flaring
tech¬
niques.
Valve
also
contains
piston
and
retainer.
Service
as
follows:
ACCURATER
(Bypass
Type)
COMPONENTS
(See
Fig.
23.)
AccuRater
piston
has
a
refrigerant
metering
hole
through
it.
Retainer
forms
a
stop
for
piston
in
refrigerant
bypass
mode,
and
a
sealing
surface
for
liquid
line
flare
connection.
To
check,
clean
or
replace
piston:
1.
Shut
off
power
to
unit.
2.
Pump
unit
down
using
Pumpdown
Procedure
des¬
cribed
in
this
Service
Manual.
3.
Remove
liquid
line
flare
connection
from
AccuRater.
4.
Pull
retainer
out
of
body,
being
careful
not
to
scratch
flare
sealing
surface.
If
retainer
does
not
pull
out
easily,
carefully
use
locking
pliers
to
remove
it.
5.
Slide
piston
out
by
inserting
a
small
soft
wire,
with
small
kinks,
through
metering
hole.
Do
not
damage
metering
hole,
sealing
surface
around
piston
cones
or
fluted
portion
of
piston.
6.
Clean
piston
refrigerant
metering
hole.
7.
Replace
retainer
O-ring
(Part
No.
99CC501052)
before
reassembling
bypass-type
AccuRater.
FLARE
NUT
Fig.
23
AccuRater
(Bypass
Type)
Components
Service
valves
provide
a
convenient
shutoff
valve
useful
for
certain
refrigeration
system
repairs.
System
may
be
pumped
down
to
make
repairs
on
low
side
without
losing
complete
refrigerant
charge.
I.
A
t
t
a
c
h
pressure
gage
to
suction
service
valve
gage
port.
2.
Frontseat
liquid
line
valve.
3.
Start
unit
in
cooling
mode.
Run
until
suction
pressure
reaches
5
psig
(35
kPa).
4.
Shut
unit
off.
Frontseat
suction
valve.
5.
Vent
remaining
pressure
to
atmosphere.
A
CAUTION
All
outdoor
unit
coils
will
hold
only
factory-supplied
amount
of
refrigerant.
Excess
refrigerant
may
cause
unit
to
relieve
pressure
through
internal
pressure
relief
valve
(indicated
by
sudden
rise
of
suction
pressure)
before
suction
pressure
reaches
5
psig
(35
kPa).
If
this
occurs,
shut
off
unit
immediately,
frontseat
suction
valve,
and
vent
remaining
pressure
to
atmosphere.
REVERSING
VALVE
-
(See
Fig.
24.)
In
heat
pumps,
changeover
between
heating
and
cooling
modes
is
accomplished
with
a
valve
that
reverses
flow
of
refrig¬
erant
in
system.
This
reversing
valve
device
is
easy
to
troubleshoot
and
replace.
The
reversing
valve
solenoid
can
be
checked
with
power
off
with
an
ohmmeter.
Check
for
continuity
and
shorting
to
ground.
With
control
circuit
(24
v)
power
on,
check
for
correct
voltage
at
solenoid
coil.
Check
for
burned
or
overheated
solenoid.
Fig.
24
Reversing
Valve
With
unit
operating,
other
items
can
be
checked,
such
as
frost
or
condensate
water
on
refrigerant
lines.
The
sound
made
by
a
reversing
valve,
as
it
begins
or
ends
defrost,
is
a
loud
whooshing
noise,
as
reversing
valve
reverses,
and
pressures
in
system
equalize.
An
experienced
service
person
detects
this
sound
and
uses
it
as
a
valuable
troubleshooting
tool.
Using
a
remote
measuring
device,
check
inlet
and
outlet
line
temperatures.
Do
not
touch
lines.
If
reversing
valve
is
operating
normally,
inlet
and
outlet
temperatures
on
appropriate
lines
should
be
close.
Any
difference
would
be
due
to
heat
loss
or
gain
across
valve
body.
Tempera¬
tures
are
best
checked
with
a
remote
reading
electronic-
type
thermometer
with
multiple
probes.
Route
thermo¬
couple
leads
to
inside
of
coil
area
through
service
valve
mounting
plate
area
underneath
coil.
Figures
25
and
26
show
test
points
on
reversing
valve
for
recording
tempera¬
tures.
Insulate
points
for
more
accurate
reading.
17

Related product manuals