47
TROUBLESHOOTING (CONT)
This unit has on−board diagnostics. Error codes are displayed on the wired remote controller and the outdoor unit microprocessor board with
colored LED lights. Table 44 explains the error codes on both.
SIZES 48 − 56
Table 44—Malfunction Status Table
ERRORS OF DEFINITION
MAIN CONTROL DISPLAY FOR OUTDOOR UNIT
INDOOR UNIT
CODE
TESTING
BOARD
CODE
YELLOW LED RED LED GREEN LED
The compressor is start up Flash 1 time
IPM current protection Flash 3 times H5 H5
IPM temperature protection Flash 5 times P8 P8
PFC current protection Flash 7 times HC HC
PFC temperature protection Flash 8 times P8 P8
Low voltage protection Flash 9 times PL PL
High voltage protection Flash 10 times PH PH
Low pressure protection Flash 11 times E3 E3
High pressure protection Flash 12 times E8 E8
High pressure switch protection Flash 13 times E1 E1
Capacitor charging error Flash 14 times PU PU
Current protection Flash 15 times E5 E5
Memory card error Flash 16 times EE EE
Compressor demagnetizing protection Flash 17 times HE HE
Compressor de-synchronizing Flash 18 times H7 H7
Compressor phase lack Flash 19 times U2 U2
Compressor phase circuit detection error Flash 20 times U1 U1
Compressor current protection Flash 21 times L9 L9
Compressor overload protection Flash 22 times H3 H3
Compressor discharge temperature protection Flash 23 times E4 E4
Lack of refrigerant or jam protection Flash 31 times F0 F0
Normal operation Flash 1 time
Frequency limitation for current protection Flash 2 times F8
Oil returning mode Flash 3 times F7 F7
Defrosting mode Flash 4 times H1 H1
Frequency limitation for IPM temperature protection Flash 5 times EU EU
Frequency limitation for PFC temperature protection Flash 6 times EU EU
Frequency limitation for compressor overload protection Flash 8 times LU
Frequency limitation for discharge temp. protection Flash 9 times F9
Frequency limitation for low pressure protection Flash 10 times Pn
Frequency limitation for high pressure protection Flash 11 times F6 F6
Discharge temperature sensor error Flash 12 times F5 F5
Outside temperature sensor error Flash 13 times F3 F3
Suction temperature sensor error Flash 15 times dc
Condenser temperature sensor error Flash 16 times A7 A7
Sub-cool temperature sensor error Flash 17 times bC
Low pressure sensor error Flash 18 times dL
High pressure sensor error Flash 19 times e1
Fan motor protection Flash 20 times H6 H6
Driving board is connected Flash 1 time
Testing board is connected Flash 2 times
Computer is connected Flash 4 times
Indoor unit 1 is connected Flash 5 times
Indoor unit 2 is connected Flash 6 times