38GL...G / 38GLS...G / 38YY...G / 38YYS...G
R-410A
Minimum clearances
B
A
C
D
E
System charge
Model
Refrigerant Suitable up to Extra charge
Extra charge (g) with indoor unit
charge (g) m g/m 42VMC---(A)N 40SMC---N
38GL(S)018G 1090 8 15 ––
38GL(S)024G 1265 8 15 220 150
38GL(S)028G 2100 8 30 100
38GL(S)036G 1980 8 40 450
38GL(S)048G 3300 8 70 300
38YY(S)018G 1530 8 15 ––
38YY(S)024G 1900 8 30 370 150
38YY(S)028G 2340 8 30 100
38YY(S)036G 2190 8 40 450
38YY(S)048G 3650 8 70 300
Mod.
18 24 28 36 48
A mm 50 100 100 100 100
B mm 250 250 250 250 250
C mm 500 500 500 500 500
D mm 50 50 100 100 100
E mm 470 470 670 670 670
F mm 400 400 400 400 400