PART6, 10
While TCDI=6.
----T40,
If the 1
st
condition and 2
nd
condition items are satisfied, then the program judges if T2 has decreased
more than 5.When T2 has decreased more than 5, enter the defrosting mode.
----No matter what value T4 is, if the machine runs with T33 for more than 120 minutes and T3
keeps lower than TCDI+4 for more than 3 minutes, the machine will enter defrosting mode no matter
if T2 drops more than 5 or not.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will finish and the machine will turn to
normal heating mode.
----T3 rises to be higher than TCDE1.
----T3 keeps to be higher than TCDE2 for 80 seconds.
----The machine has run for 10 minutes in defrosting mode.
While TCDE1=15, TCDE2=8 for 18k, 24k model. TCDE1=12, TCDE2=8 for other models.