PART5, 2
3. Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
42/38LUVH025N-1
3/8’’
(Ф9.53)
1/4’’
(Ф6.35)
5
8
20
20
42/38LUVH035N-1
42/38LUVH045N-1
1/2’’
12.7)
1/4’’
(Ф6.35)
5
8
20
20
42/38LUVH055N-1
42/38LUVH065N-1
42/38LUVH075N-1
5/8’’
(Ф16.0)
3/8’’
(Ф9.53)
5
10
25
40
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meter