3.2.4 Condenser temperature protection
---55<T3<60, the compressor frequency will decrease to the lower level until to F1 and then runs
at F1.If T3<54, the compressor will keep running at the current frequency.
---T3<52, the compressor will not limit the frequency and resume to the former frequency.
---T3>60 for 5 seconds, the compressor will stop until T3<52.
3.2.5 Evaporator temperature protection
---T2<0, the compressor will stop and restart when T2>=5.
---0℃≦T2<4, the compressor frequency will be limited and decreased to the lower level
---4≤T2≤7, the compressor will keep the current frequency.
---T2>7, the compressor frequency will not be limited.
3.3 Heating Mode
3.3.1 Compressor running rules
The maximum operation frequency of the compressor after starting submits to the following rule.