DIAGNOSIS AND SOLUTION (CONT)
Zero Crossing Detection Error Diagnosis and Solution (EH02)
Description: When the PCB does not receive a zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal.
Recommended parts to repair:
Connection wires
Indoor main PCB
Troubleshooting and Repair:
Note: Zero crossing detection error is only valid for the unit with AC fan motor. For other models, this error does not apply.
Check the connections and
power supply.
Correct the connections. Turn on the
unit when the power supply is on.
NO
Indoor main PCB is defective.
Replace the indoor main PCB.
YES
Is it normal?