PC 02 (Top Temperature Compressor Protection or High Temperature IPM Module Protection of
Diagnosis and Solution)
Description: For some models with overload protection, If the sampling voltage is not 5V, the LED displays the failure. If the IPM module
temperature is higher than a certain value, the LED displays a failure code.
Recommended parts to prepare:
Connection wires
Outdoor PCB
IPM module board
High pressure protector
System blockage
s
Troubleshooting and repair:
Check if the air ow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units .
Yes
No
Yes
Yes
Turn o the power supply and turn
it on 10 minutes later.
Check if the temperature of the
compressor Top is more than 90 °C.
No
Check if the refrigerant
system is normal.
Repair the refrigerant
system .
Replace the outdoor control PCB.
Yes
Check if all the connections
especially
the connection of OLP (Over Load
Protector) sensor is good .
Correct the connection .No
Measure the resistance
between the two OLP ports.
Is it zero?
Yes
Replace the OLP.No
Replace the outdoor control PCB .Yes
No