38MBRC: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
PC 06 (Discharge Temperature Protection of Compressor Diagnosis and Solution)
Description: If the compressor discharge temperature exceeds a certain level for nine seconds, the compressor ceases operation and the LED displays
the failure code.
Recommended parts to prepare:
• Connection wires
• Discharge temperature sensor
• Additional refrigerant
• Outdoor main PCB
Troubleshooting and repair:
No
Correct the wiring connection
Stop the leak and add refrigerant
Yes
Replace high pressure valve assembly
Yes
No
YES
Is refrigerant leaking ?
Are the
compressor discharge
temperature sensor and PCB
connected properly according
to the wiring
diagram?
Is the compressor discharge
temperature more than
115 °C (R410 a)
108°C(R32) ?
Is the value normal ?
Measure the resistance value
of compressor discharge
temperature sensor
YES
NO
Replace outdoor main PCB.
Does a problem still exist ?