38MGRBQ: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
43
DIAGNOSIS AND SOLUTION (CONT)
Water-level alarm malfunction diagnosis and solution
Troubleshooting
ERROR CODE
REFER TO INDOOR UNIT SERVICE MANUAL
MALFUNCTION DECISION
CONDITIONS
If the sampling voltage is not 5V, the LED displays the failure code.
SUPPOSED CAUSES
Wiring mistakes
Faulty water-level switch
Faulty water pump
Faulty indoor PCB
Is the water-level switch
inserted well?
No
Insert the water level switch well-
Is the water
-level switch
broken?
Yes
Replace the water-level switch
Replace the water pump. Is
the malfunction still
unresolved?
Yes
No
Yes
Replace the indoor main PCB.
Power off, then restart the unit 3 minutes
later. Is it still displaying the error code?
Yes