EasyManua.ls Logo

Carrier 38QH - Service Sentry Control; Outdoor Thermostats

Carrier 38QH
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
capacitor.
Fan
motor
is
equipped
with
thermal
overload
device
in
motor
windings
which
may
open
under
adverse
operating
conditions.
Allow
time
for
motor
to
cool
so
device
can
reset.
Further
checking
of
motor
can
be
done
with
an
ohmmeter.
Set
scale
on
R
x
1
position,
check
for
continuity
between
3
leads.
Replace
motors
that
show
an
open
circuit
in
any
of
the
windings.
Place
one
lead
of
ohmmeter
on
each
motor
lead.
At
same
time,
place
other
ohmmeter
lead
on
motor
case
(ground).
Replace
any
motor
that
shows
resistance
to
ground.
Obviously
any
motor
that
shows
signs
of
arcing,
burning
or
over¬
heating
should
be
suspect
and
replaced.
SERVICE
SENTRY
CONTROL
BOARD
Service
Sentry
control
provides
immediate
warning
when
out¬
door
heat
pump
requires
servicing.
It
turns
on
indoor
thermostat
light
if
compressor
doesn't
operate
for
either
heating
or
cooling.
This
enables
owner
to
obtain
speedy
heat
pump
service
during
heating
season,
reducing
supplementary
electric
heat
costs,
and
during
cooling
season,
reducing
period
of
heat
discomfort.
Fig.
14.
Fig.
14
Service
Sentry
Control
Use
Service
Sentry
control
with
single-phase
Carrier
heat
pumps
equipped
with
24-v
control
circuit.
Connect
black,
orange
and
red
pigtails
(24
v)
on
Service
Sentry
to
outdoor
unit
control
circuit
terminal
board.
See
Fig.
15
and
wiring
diagram
on
unit.
An
extra
control
wire
is
required
between
L
terminals
on
outdoor
unit,
indoor
unit
and
thermostat
subbase
(the
L
terminal
is
currently
being
added
to
outdoor
and
indoor
unit
termi¬
nal
blocks).
If
units
do
not
already
have
L
terminal,
splice
control
wire
between
L
terminals
on
Service
Sentry
and
thermostat
subbase.
Terminal
L
is
labeled
terminal
X
on
some
thermostat
subbases
(all
future
subbases
will
read
terminal
L).
Connect
all
field
line
power
wires
to
unit
in
usual
manner.
However,
route
one
field
line
power
supply
wire
through
metallic
loop
on
bottom
of
Service
Sentry,
then
to
normal
unit
connection.
On
015
(230-1-60)
and
018
(230-1-60)
units,
pass
supply
wire
through
metallic
loop
twice,
as
shown
in
Fig.
14
and
15.
On
all
other
units,
pass
supply
wire
through
loop
only
once.
Refer
to
Fig.
15
for
wiring
connections
when
Service
Sentry
and
solid-state
Time
Guard
II
accessories
are
used.
The
Service
Sentry
is
an
accessory
device.
On
heat
pump
DL
and
CD
option
packages,
a
slightly
different
version
of
Service
Sentry
is
installed
as
standard
equip¬
ment.
It
functions
almost
identically
to
accessory
Service
Sentry
except
that
it
locks
out
compressor
under
certain
adverse
operating
conditions.
System
is
manually
reset
by
shutting
it
off
at
thermostat
subbase,
then
turning
it
back
on.
If
adverse
condition
is
corrected,
system
restarts.
One
example
of
an
adverse
condition
would
be
if
system
is
located
in
a
desert
climate
where
high
operating
temperatures
may
cause
system
to
shut
down
on
the
high-
pressure
switch,
or
on
the
compressor
internal
overload.
Service
Sentry
Requires
2
Inputs:
1.
It
must
sense
a
24-v
input
from
thermostat.
As
thermo¬
stat
calls
for
heating
or
cooling,
it
supplies
24
v
to
Service
Sentry
device.
2.
A
current
transformer
(or
induction
loop)
similar
to
a
clamp-on
ammeter
senses
current
draw
in
the
com¬
pressor
lead.
Induction
loop
must
sense
a
minimum
current
draw
when
thermostat
is
calling
for
heating
or
cooling.
NOTES:
1.
On
a
single-phase
compressor,
induction
loop
senses
current
in
common
leg.
2.
On
a
3-phase
compressor,
induction
loop
senses
current
in
one
of
the
phases.
Troubleshooting
Service
Sentry
device
is
easy.
With
thermostat
calling
for
heating
or
cooling
and
compressor
running,
indoor
thermostat
light
should
be
off.
If
on,
check
for
wiring
errors
or
replace
the
Service
Sentry.
To
check
for
correct
operation,
shut
off
circuit
breaker
or
disconnect
switch
to
outdoor
unit
while
it
is
running.
Signal
light
on
thermostat
should
light.
If
this
does
not
occur,
check
for
wiring
errors
or
replace
the
Service
Sentry.
A
CAUTION
If
Service
Sentry
needs
replacing,
shut
off
all
power
to
unit
before
attempting
repairs.
OUTDOOR
THERMOSTATS
(See
Fig.
16.)
Out¬
door
thermostat
brings
on
stages
of
electric
heat
as
out¬
door
temperature
and
heat
pump
output
drops.
Setting
at
which
thermostat
closes
is
variable,
depending
on
design
of
system.
It
is
set
at
time
of
installation
and
should
not
be
changed
without
good
reason.
Up
to
2
outdoor
thermostats
may
be
installed.
Some
systems
may
not
have
any
thermostat.
Although
these
devices
are
installed
in
control
circuit
(24
v),
turn
off
all
power
to
unit
before
attempting
to
troubleshoot
thermostat.
Use
a
standard
ohmmeter
to
check
for
continuity
through
thermostat.
If
you
suspect
thermostat
is
out
of
calibration,
use
calibrated
electronic
thermometer
to
determine
correct
outdoor
temperature.
Insert
a
screw¬
driver
blade
in
adjustment
slot
and
turn
thermostat
switch
until
it
closes.
Observe
this
using
ohmmeter
across
switch.
Read
temperature
setting
when
switch
closes.
It
should
be
close
to
reading
observed
using
electronic
thermometer.
Any
setting
within
±
5
degrees
is
acceptable.
11

Other manuals for Carrier 38QH

Related product manuals