Carrier 38QH024 - Strainer, Accumulator, and Charging

Carrier 38QH024
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.
Remove
2
(015,018)
or
4
(024,060)
screws
at
base
of
coil
(located
at
end
of
large
vertical
wires
in
coil
support).
6.
Lift
coil
vertically
from
basepan,
place
aside
carefully.
NOTE:
When
coil
is
removed,
use
opportunity
to
also
remove
liquid
line
strainer.
Strainer
location
is
identified
by
label
on
liquid
line.
7.
Reverse
procedure
to
reinstall
coil.
COIL
CLEANING
(See
Fig.
28,
29.)
For
best
unit
efficiency,
clean
outdoor
coil
prior
to
start
of
each
heating
or
cooling
season.
Shut
off
all
power
to
unit
if
coil
is
equipped
with
louvered
casing.
Refer
to
Cabinet
Servic¬
ing
for
casing
removal
procedure.
To
clean
coil:
A
CAUTION
Coil
fin
damage
can
result
in
higher
operating
costs
or
compressor
damage.
Do
not
use
flame,
high-
pressure
water,
steam,
volatile
or
corrosive
cleaners
on
fins
or
tubing.
Clean
coil
using
vacuum
cleaner
and
its
crevice
tool.
Move
crevice
tool
vertically
,
close
to
area
being
cleaned,
making
sure
tool
touches
only
the
dirt
on
the
fins
and
not
the
fins.
To
prevent
fin
damage,
do
not
scrub
fins
with
tool
or
move
tool
horizontally
against
fins.
If
oil
deposits
are
present,
spray
coil
with
ordinary
household
detergent.
Wait
10
minutes,
proceed
to
next
step.
Using
garden
hose,
spray
coil
vertically
downward
with
constant
stream
of
water
at
moderate
pressure.
Keep
nozzle
at
a
15
to
20
degree
angle,
about
3
in.
(76
mm)
from
coil
face
and
18
in.
(457
mm)
from
tube.
Spray
so
debris
is
washed
out
of
coil.
Reinstall
louvered
casing
if
necessary.
,
Restore
power
to
unit.
LIQUID
LINE
STRAINER
Heating
and
cooling
models
are
equipped
with
a
strainer
in
liquid
line.
It
is
marked
with
identifying
sticker.
Strainer
picks
up
harm¬
ful
debris
that
may
be
in
system.
If
it
becomes
plugged,
system
does
not
perform
properly.
System
pressures
become
abnormal
and
compressor
may
become
very
hot
and
cycle
off
on
its
protection
device.
If
strainer
is
plugged,
it
can
be
easily
removed.
Shut
off
all
power
to
unit.
Bleed
off
all
refrigerant
from
system.
19