EasyManua.ls Logo

Carrier 38QN - Motor Winding Electrical Tests; Ground Circuit Test; Short Circuit Test

Carrier 38QN
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
POWER
OFF'
OHMMETER
O-IO
n
SCALE
9
5.2
n
b
<?>
0
.
61
!
6
?
5.8
ll
A
(example)
TO
DETERMINE
INTERNAL
CONNECTIONS
OF
SINGLE¬
PHASE
MOTORS
(C,S,R)
except
shaded-pole
Deduction:
(D-d)
(greatest
resistance)
Run
Winding
(R)
5.811
(ohm)
Start
Winding
(S)
(D—<D
(smallest
resistance)
(2)
is
common
(C)
0.611
by
elimination
CD—©
(remaining
resistance)
(2)
is
common,
5.211
therefore
(T)
is
Start
Winding
(S)
(3)
is
Run
Winding
(R)
Fig.
17
Determining
Internal
Connections
terminal
must
be
common
(C).
Greatest
resistance
between
common
(C)
and
another
terminal
indicates
start
winding
because
it
has
more
turns.
This
terminal
is
start
(S).
Remaining
terminal
will
be
run
winding
(R).
NOTE:
If
there
is
an
internal
line
break
protector,
it
must
be
closed.
Three-Phase
Motors
See
Fig.
18.
Resistance
readings
between
all
3
sets
of
windings
should
be
the
same.
All
compressors
are
equipped
with
internal
motor
pro¬
tection.
If
motor
becomes
hot
for
any
reason,
protector
opens.
Compressor
should
always
be
allowed
to
cool
and
protector
to
close
before
troubleshooting.
Always
turn
off
all
power
to
unit
and
disconnect
leads
at
com¬
pressor
terminals
before
taking
readings.
Most
common
motor
failures
are
due
to
either
an
open,
grounded
or
short
circuit.
Directions
below
are
specifi¬
cally
for
single-phase
units,
however,
they
also
apply
to
3-phase
compressors.
When
a
single-phase
compressor
fails
to
start
or
run,
3
tests
can
help
determine
the
problem.
First,
all
possible
external
causes
should
be
eliminated,
such
as
overloads,
improper
voltage,
pressure
equalization,
defective
capacitor(s),
relays,
wiring,
etc.
If
compressor
has
internal
line
break
overload,
be
sure
it
is
closed.
Open
Circuit
To
determine
if
any
winding
has
a
break
in
the
internal
wires
and
current
is
unable
to
pass
through:
Be
sure
all
power
is
off.
Discharge
all
capacitors.
Remove
wires
from
terminals
C,
S
and
R.
Use
an
ohmmeter
on
0-1000
ohm
scale
to
check
resistance
from
C-R,
C-S
and
R-S.
Because
winding
resistances
are
usually
less
than
10
ohms,
each
reading
appears
to
be
approximately
zero
ohm.
If
resistance
remains
at
1000
ohms,
an
open
or
break
exists
and
compressor
should
be
replaced.
Be
sure
internal
porarily
open.
line
break
overload
is
not
tern-
J
Ground
Circuit
To
determine
if
a
wire
has
broken
or
come
in
direct
contact
with
shell,
causing
a
direct
short
to
ground:
Be
sure
all
power
is
off.
Discharge
all
capaci¬
tors.
Remove
wires
from
terminals
C,
S
and
R.
On
hermetic
compressors,
allow
crankcase
heaters
to
remain
on
for
several
hours
before
checking
motor
to
ensure
windings
are
not
saturated
with
refrigerant.
Use
an
ohmmeter
on
R
x
10,000
ohm
scale.
A
megohmmeter
may
be
used
in
place
of
ohmmeter
(follow
manufacturer’s
instructions).
Place
one
meter
probe
on
ground
or
on
compressor
shell.
Make
a
good
metal-to-metal
contact.
Place
other
probe
on
terminals
C,
S
and
R
in
sequence.
Note
meter
scale.
If
reading
of
zero
or
low
resistance
is
obtained,
motor
is
grounded.
Replace
compressor.
A
compressor
of
one-ton
capacity
or
less
is
probably
grounded
if
resistance
is
below
one
million
ohms.
On
larger
size
single-phase
compressors,
resistance
to
ground
should
not
be
less
than
1000
ohms
per
volt
of
operating
voltage.
Example:
230-1-60
...
230
x
1000
=
230,000
ohms
minimum.
Short
Circuit
To
determine
if
any
wires
within
windings
have
broken
through
their
insulation
and
made
contact
with
other
wires,
thereby
shorting
all
or
part
of
the
winding(s):
First,
be
sure
the
following
conditions
are
met:
1.
Correct
motor
winding
resistances
must
be
known
before
testing,
either
from
previous
readings
or
from
manufacturer’s
specifications.
2.
Temperature
of
windings
must
be
as
specified,
usually
about
70
F.
3.
Resistance
measuring
instrument
must
have
an
accu¬
racy
within
±
5%
-
10%.
This
requires
accurate
ohmmeter
(such
as
a
Wheatstone
bridge
or
null
balance-type
instrument).
4.
Motor
must
be
dry
or
free
from
direct
contact
with
liquid
refrigerant.
Make
This
Critical
Test
(Not
advisable
unless
above
conditions
are
met.)
Be
sure
all
power
is
off.
Discharge
all
capacitors.
Remove
wires
from
terminals
C,
S
and
R.
Place
instrument
probes
together,
determine
probe
and
lead
wire
resistance.
Check
resistance
readings
from
C-R,
C-S
and
R-S.
Subtract
instrument
probe
and
lead
14

Other manuals for Carrier 38QN

Related product manuals