Carrier 38QN - Defrost Thermostats

Carrier 38QN
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TIME
GUARD
U
24
VAC
CONTACTOR
COMMON
SIDE
1
TRANS.
|
-
FIELD
CONTROL
WIRING
(\F
used)
©
ELECTRONIC-
TIME
GUARD
!
PART
NO
HN67PA024
INPUT
24
V
60
HZ
5
MINUTE
RECYCLE
DELAY
TIMER
6LK
DENOTES
CLOSED
CONTACTS
TIME
GUARD
II
SEQUENCE
CHART
ACCESSORY
TIME
GUARD
II
DEVICE
CUT
YELLOW
WIRE
NOTE:
When
accessory
Time
Guard
II
is
used
with
accessory
Service
Sentry
control
on
38QH,QN,QS
units,
refer
to
wiring
instructions
packed
with
Service
Sentry
control.
MOUNTING
ACCESSORY
TIME
GUARD
II
ON
MODEL
38QH,QS,QN
TIME
GUARD
II
CONTROL
WIRING
CONNECTIONS
FOR
38QH,QN,QS
UNITS
Fig.
8
Solid-State
Time
Guard
II
Description
A
CAUTION
Wear
safety
glasses
and
gloves
when
working
with
refrigerants.
Apply
heat
with
a
torch
to
solder
joint
and
remove
switch.
Wear
safety
glasses
when
using
torch.
Have
quenching
cloth
available.
Oil
vapor
in
line
may
ignite
when
switch
is
removed.
Braze
in
1
/
4-in.
flare
fitting
and
screw
on
replacement
pressure
switch.
Wear
safety
glasses,
observe
all
safety
precautions.
Hi
g
h
-
P
r
essure
Switch
Located
on
discharge
line,
protects
against
high
discharge
pressures
caused
by
such
events
as
overcharge,
condenser
fan
motor
failure,
system
restriction,
etc.
It
opens
on
pressure
rise
at
about
425
psi.
If
system
pressures
go
above
this
setting
during
abnormal
condition,
switch
opens.
Do
not
attempt
to
simulate
these
system
abnormalities,
as
high
pressures
pose
a
serious
safety
hazard.
High-pressure
switch
is
also
checked
with
an
ohmmeter
similar
to
checking
low-
pressure
switch.
If
system
pressure
is
below
425
psi,
switch
shows
continuity.
It
is
replaced
in
same
manner
as
low-
pressure
switch.
Observe
all
safety
precautions.
Liquid
Line
Pressure
Switch
Located
on
liquid
line,
used
in
heat
pump
only.
Function
is
similar
to
con¬
ventional
low-pressure
switch.
Because
heat
pumps
experience
very
low
suction
pressures
during
normal
system
operation,
a
conventional
low-pressure
switch
cannot
be
installed
on
suction
line.
Switch
is
installed
in
liquid
line
instead
and
acts
as
loss-of-charge
protector.
It
operates
identically
to
low-pressure
switch
except
it
opens
at
5
psi.
Troubleshooting
and
removing
this
switch
is
identical
to
procedures
used
on
other
switches.
Observe
same
safety
precautions.
DEFROST
THERMOSTATS
Defrost
thermostat
signals
heat
pump
that
conditions
are
right
for
defrost
or
that
conditions
have
changed
to
terminate
defrost.
It
is
a
thermally
actuated
switch
clamped
to
liquid
line
to
sense
its
temperature.
Normal
temperature
range
is:
closed
at
27
±
5
F,
open
at
80
±
5
F.
Since
defrost
thermostat
is
the
heart
of
the
defrost
system,
its
troubleshooting
procedure
is
described
below.
PRINTED-CIRCUIT
CONTROL
BOARD
Solid-
state
defrost
control
used
on
38QH,QN,QS
heat
pumps
replaces
electro-mechanical
timer
and
defrost
relay
found
on
previous
Carrier
Chronotemp
defrost
systems.
De¬
frost
control
board
can
be
set
to
check
need
for
defrost
8