EasyManua.ls Logo

Carrier 38QUS012D8S - Page 121

Carrier 38QUS012D8S
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Electrical Control System 119
2.4.4 Outdoor Units
2.4.4.1. Compressor Driven Chip EEPROM Malfunction
Malfunction conditions
Main PCB chip does not receive feedback from EEPROM chip
Possible causes
Installation mistakes
Faulty PCB
Yes
Replace the outdoor main
PCB
Replace the outdoor main
PCB
Power off, then restart the
unit 2 minutes later. Does the
malfunction still remain?
Power off, then restart the
unit 2 minutes later. Does the
malfunction still remain?
Compressor driven chip
EEPROM malfunction
Compressor driven chip
EEPROM malfunction

Related product manuals