42
Fig. 29 —38VMA144RDL5-1
Table 36 —38VMA144RDL5-1
Fig. 30 —38VMA144RDL6-1
Table 37 —38VMA144RDL6-1
NOTE: When silent mode is set, the unit's capacity is limited. The unit will automatically exit silent mode if high pressure exceeds 522
psi. The unit will automatically return to silent mode once high side pressure falls below 479 psi.
38VMA144RDL5-1 63 125 250 500 1000 2000 4000 8000 dB(A)
Standard 60Hz 70.0 73.6 61.0 57.0 52.1 49.7 42.8 38.0 60.7
Low noise mode 60Hz 54.2 54.9 46.9 51.7 44.0 46.2 40.9 36.9 52.9
38VMA144RDL6-1 63 125 250 500 1000 2000 4000 8000 dB(A)
Standard 60Hz 70.5 74.8 63.6 61.7 54.1 49.0 42.0 39.1 62.6
Low noise mode 60Hz 61.2 57.4 48.0 53.4 44.0 42.4 37.1 35.8 52.8