Table 9 - Outdoor unit heating capacity calculation
Outdoor Unit Capacity x 1000 BTU Outdoor Unit Capacity (HP) D
72 8
96 10
120 12
144 14
QHo: Outdoor Unit Heating Capacity
QHo = QHi x D/∑DRound number
T2A correction factor E
T = 102F (default)
QHr: Outdoor Unit Real Heating Capacity
QHr = QHo + E
For example
Outdoor Unit 72 + 96Heating Indoor Unit (12K x 6) + (18K x 6)T1 = 63FTS = 70FT4 = 45FT2A (average) = 93F
T1 TS = 63 70 = -7so B = 2
T4 = 45so C = 100%
T2A (average) = 93Fso E = 6
QHi = ∑(AxB) x C =1.2 x 2 x 6 + 2.0 x 2 x 6x 100% = 38.4Round number39
72 outdoor unit capacityQHo = QHix D / ∑D = 39 x 8 /8 + 10= 17.3Round number18
96 outdoor unit capacityQHo = QHix D / ∑D = 39 x 10 /8 + 10= 21.6Round number22
72 outdoor unit actual capacityQHr = QHo + E =18 + 6 = 24From the frequency table70Hz
96 outdoor unit actual capacityQHr = QHo + E = 22 + 6 = 28From the frequency table78Hz
NOTES:
TS: Indoor unit setting temperature
T1: Room temperature
T2A: Temperature of evaporator inlet
T2B Temperature of evaporator outlet
T4: Ambient temperature