Basic Control
NORMAL OPERATION
Table 24 —Cooling Operation
Table 25 —Heating Operation
NOTE: Heating operation is not functional at an outdoor air temperature of 77°F or more.
LEGEND:
INV – Inverter
SV – Solenoid Valve
COMPONENT NORMAL OPERATION REMARK
Compressor (INV) Capacity demand control To build pressure difference
Outdoor Unit fan (FAN) Cooling fan control -
4-Way Valve OFF -
Electronic Expansion Valve (EEV) Discharge temperature control Adjust refrigerant flow rate to protect compressor
Fast Oil Return Valve (SV4) 17 minutes OFF then 3 minutes ON -
Hot Gas Bypass Valve (SV5) OFF -
Spraying Liquid Valve (SV6) Discharge temperature protection control -
COMPONENT NORMAL OPERATION REMARK
Compressor (INV) Capacity demand control To build pressure difference
Outdoor Unit fan (FAN) Heating fan control -
4-Way Valve ON -
Electronic Expansion Valve (EEV) Discharge temperature control Adjust refrigerant flow rate to protect compressor
Fast Oil Return Valve (SV4) 17 minutes OFF then 3 minutes ON -
Hot Gas Bypass Valve (SV5) OFF
Open based on conditions at startup stage (after defrosting
and oil return operation)
Spraying Liquid Valve (SV6) Discharge temperature protection control -