Capacity code of indoor and outdoor units
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2-1, Table 2-2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable
indoor units differs based on the height difference between the indoor units.
When the height difference between the indoor units is 15 m or less: Up to 200% of the capacity code
(Equivalent to HP) of the outdoor unit.
When the height difference between the indoor units is over 15 m: Up to 105% of the capacity code.
If
outdoor unit capacity.
If the system diversity is more than 135%, check the maximum number of indoor unit connections in table 2-1,
2-2, and then turn on DIP switch 3 of SW103 on the interface P.C. boards.
Table 2-1 [Diversity 135%]
Table 1
Indoor unit
capacity rank
Capacity code
Equivalent to HP
Equivalent to
capacity
007 0.8 2.2
008 0.9 2.5
009 1 2.8
010 1.1 3.2
012 1.25 3.6
014 1.5 4
015 1.7 4.5
017 1.85 5
018 2 5.6
020 2.25 6.3
024 2.5 7.1
027 3 8.0
030 3.2 9.0
036 4 11.2
048 5 14.0
056 6 16.0
072 8 22.4
096 10 28.0
112 12 33.5
128 14 40.0
144 16 45.0
192 20 56.0
Model Name
[Standard]
Capacity code
Max. No.
of indoor
units
Total
capacity of
indoor units
Diversity
(%)
Equivalent
to HP
Equivalent
to capacity
8 22.4 13 30.2 135%
10 28.0 16 37.8 135%
12 33.5 20 45.2 135%
14 40.0 23 54.0 135%
16 45.0 27 60.7 135%
18 50.4 30 68.0 135%
20 56.0 33 75.6 135%
22 61.5 37 83.0 135%
24 67.0 40 90.4 135%
26 73.0 43 98.5 135%
28 80.0 47 108.0 135%
30 83.9 50 113.2 135%
32 89.5 54 120.8 135%
34 95.0 57 128.2 135%
36 100.5 60 135.6 135%
38 106.5 64 143.7 135%
40 113.0 67 152.5 135%
42 117.5 70 158.6 135%
44 123.0 71 166.0 135%
46 128.5 72 173.4 135%
48 134.0 73 180.9 135%
50 140.0 74 189.0 135%
52 146.0 75 197.1 135%
54 151.0 76 203.8 135%
56 156.5 77 211.2 135%
58 162.0 78 218.7 135%
60 167.5 79 226.1 135%
62 174.0 80 234.9 135%
64 179.5 81 242.3 135%
66 184.5 82 249.0 135%
68 190.0 83 256.5 135%
70 195.5 84 263.9 135%
72 201.0 85 271.3 135%
74 207.0 86 279.4 135%
76 213.0 87 287.5 135%
78 219.0 88 295.6 135%
80 223.5 90 301.7 135%
82 229.0 92 309.1 135%
84 234.5 94 316.5 135%
86 240.5 96 324.6 135%
88 246.5 98 332.7 135%
90 252.5 100 340.8 135%
92 259.0 102 349.6 135%
94 262.5 104 354.3 135%
96 268.0 106 361.8 135%
98 274.5 108 370.5 135%
100 280.0 110 378.0 135%
38VT0081
38VT0101
38VT0121
38VT0141 (014A)
38VT0161
38VT018
38VT0201
38VT0221
38VT0241
38VT0261
1
38VT2811
38VT3011
38VT3211
38VT3411
38VT3611
38VT3811
38VT4011
38VT4211
38VT4411
38VT4611
38VT4811
38VT5011
38VT5211
38VT5411
38VT5611
38VT5811
38VT6011
38VT6211
38VT6411
38VT6611
38VT6811
38VT7011
38VT7211
38VT7411
38VT7611
38VT7811
38VT8011
38VT8211
38VT8411
38VT8611
38VT8811
38VT9011
38VT9211
38VT9411
38VT9611
38VT9811
38VT10011
40VU
S is include in the system, total indoor capacity code must be between 50% and 105% of