– 21 –
Table 3-3
Corrective amount of refrigerant varies for Smart 4 way cassete
Indoor unit capacity rank 009 012 015 018 024 027 030 036 048 056
Capacity code (Equivalent to HP) 1 1.25 1.7 2 2.5 3 3.2 4 5 6
Corrective amount of refrigerant (kg) 0.2 0.6
Charging of refrigerant
Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Table 3-4
Corrective amount of refrigerant varies for Smart 4 way cassete Cooling Only Model
Indoor unit capacity rank 009 012
Capacity code (Equivalent to HP)
Corrective amount of refrigerant (kg) 0.4
11.25
Table 3-1
Corrective amount of refrigerant varies according to indoor unit capacity rank.
Table 3-2
Corrective amount of refrigerant varies for DX Coil Interface
System HP Combionation HP Conpensation by System HP (kg)
50 26 24 - - - 3.0
52 26 26 - - - 3.0
54 22 20 12 - - 0.2
56 22 22 12 - - 2.7
58 24 22 12 - - 2.7
60 24 24 12 - - 2.7
62 24 24 14 - - 2.7
64 26 26 12 - - 2.7
66 22 22 22 - - 4.5
68 24 24 20 - - 2.0
70 24 24 22 - - 4.5
72 24 24 24 - - 4.5
74 26 24 24 - - 4.5
76 26 26 24 - - 4.5
78 26 26 26 - - 4.5
80 24 22 22 12 - 4.2
82 24 24 22 12 - 4.2
84 24 24 24 12 - 4.2
86 26 24 24 12 - 4.2
88 26 26 24 12 - 4.2
90 26 26 26 12 - 4.2
92 26 26 26 14 - 4.2
94 24 24 24 22 - 6.0
96 24 24 24 24 - 6.0
98 26 26 24 22 - 6.0
100 26 26 24 24 - 6.0
102 26 26 26 24 - 6.0
104 26 26 26 14 12 3.9
106 26 26 22 20 12 3.2
108 26 26 24 24 8 5.7
110 26 26 24 22 12 5.7
112 26 26 24 24 12 5.7
114 26 26 26 24 12 5.7
116 26 26 26 24 14 5.7
118 24 24 24 24 22 7.5
120 24 24 24 24 24 7.5
Table 2
Liquid pipe dia. (mm) 6.4 9.5 12.7 15.9 19.1 22.2 25.4
Additional refrigerant amount per 1 m
liquid pipe (kg/m)
0.025 0.055 0.105 0.160 0.250 0.350 0.470
Indoor unit Capacity
rank
007 008 009 010 012 014 015 017 018 020 024 027 030 036 048 056 072 096 112 128 144 192
Capacity code
(Equivalent to HP)
0.8 0.9 1 1.1 1.25 1.5 1.7 1.8 2 2.25 2.5 3 3.2 4 5 6 8 1 12 14 16 20
Corrective amount of
refrigerant (kg)
0.2 0.4 0.6 1.0 1.4
For the TA, DDC type, the corrective amount of refrigerant is below.
Capacity code
(Equivalent to HP)
8 101214161820222426283032343638404244464850
Corrective amount of
refrigerant (kg)
1.4 1.8 2.1 2.5 2.9 3.2 3.6 3.9 4.3 4.6 5.0 5.3 5.8 6.1 6.5 6.8 7.2 7.5 7.9 8.2 8.6 8.9
Capacity code
(Equivalent to HP)
52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94
Corrective amount of
refrigerant (kg)
9.3 9.7 10.0 10.4 10.8 11.1 11.5 11.8 12.2 12.5 12.9 13.3 13.6 14.0 14.3 14.7 15.1 15.4 15.8 16.1 16.5 16.9
Capacity code
(Equivalent to HP)
96 98 100 102 104 106 108 110 112 114 116 118 120
Corrective amount of
refrigerant (kg)
17.2 17.6 17.9 18.3 18.7 19.0 19.4 19.7 20.1 20.5 20.8 21.2 21.5
* TF Type : The corrective amount of refrigerant is 0 kg.
40VAMR-C8FATEE, 40VAM--C8FATEE