– 41 –
<Collective trial>
Start operation
1
Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “FAN” mode: SW01=[2], SW02=[9], SW03=[1].
7-segment display
[A]
[C ]
[F ]
[B]
[ ]
[ ]
2
Press and hold SW04 for more than 2 seconds.
NOTE
You cannot change the temperature setting during the test run.
Abnormality is detected as usual.
The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display
[A]
[C ]
[F ]
[B]
[ - C ]
[ - F ]
Stop operation
1
Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
Interface P.C. board
Press switch
Rotary switches
7-segment
display [A]
7-segment
display [B]
NOTE
• The test run is a forced run that ignores the set temperature. Be sure to stop the test run after work, paying
attention to the room temperature.
• After 60 minutes, the test run will be completed to protect the equipment, and the normal operation will be
started according to the set temperature. However, note that if the remote controller less setting is set, some
indoor models will not complete the test run even after 60 minutes have passed.