Electrical data
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
Time-delay fuse.
Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
** If wire is applied at ambient greater than 30
°
C (86
°
F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable
(NM), trade name ROMEX, shall be that of 60
°
C (140
°
F) conductors, per the NEC (ANSI/NFPA 70) Article 336-36.
If other than uncoated (non-plated), 60
°
or 75
°
C (140
°
or 167
°
F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than
10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
NOTE:
Control circuit is 24v on all units and requires external power source. Copper wire must be used from disconnect to unit. All motors/compressors contain
internal overload protection. Model Size 042 MCA value greater than 048 due to UL testing.
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning, Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
RLA
— Rated Load Amps
OUTDOOR
UNIT
V/PH
60 Hz
OPER VOLTS* COMPR
FAN
FLA MCA
MIN WIRE
SIZE**
60
°
C/75
°
C
MAX
LENGTH
(Ft)‡
60
°
C/75
°
C
MAX FUSE†
OR HACR
TYPE CKT
BKR AMPSMax Min LRA RLA
018-33, 34
208-230/1 253 197
49.0 9.8 0.5 12.8 14/14 70/70 20
024-35
61.0 11.4 0.5 14.8 14/14 50/45 20
024-36
61.0 11.7 0.5 15.1 14/14 50/45 20
030-36
73.0 14.7 1.4 19.8 14/14 35/35 30
030-37
75.0 13.7 1.4 18.5 14/14 40/40 30
036-36
105.0 18.0 1.4 23.9 12/12 50/50 35
036-37
92.0 17.5 1.4 23.3 12/12 50/50 35
042-32
124.0 27.8 1.4 36.2 8/8 80/80 50
042-33
129.0 28.0 1.4 36.4 8/8 80/80 50
048-32
140.0 24.4 1.4 31.9 8/8 90/90 50
048-33
129.0 23.7 1.4 31.0 8/8 95/90 50
060-32
165.0 30.8 1.4 39.9 8/8 75/70 60
060-33
169.0 30.8 1.4 39.9 8/8 75/70 60
030-57
208/230/3 253 187
68.0 9.0 1.4 12.7 14/14 70/65 15
036-56
90.0 11.4 1.4 15.7 14/14 50/50 20
036-57
75.0 11.0 1.4 15.2 14/14 50/50 20
042-52
92.0 16.4 1.4 21.9 12/12 60/60 30
042-53
99.0 15.9 1.4 21.3 12/12 60/60 30
048-52
105.0 14.1 1.4 19.0 14/14 40/40 25
048-53
99.0 13.5 1.4 18.3 14/14 45/40 25
060-52
123.0 17.0 1.4 22.9 12/12 55/55 35
060-53
123.0 18.5 1.4 24.5 12/12 55/55 35
036-66
460/3 506 414
45.0 6.2 0.8 8.6 14/14 95/95 15
036-67
37.5 5.6 0.8 7.8 14/14 95/95 15
042-63
49.5 8.7 0.8 11.7 14/14 140/140 15
048-62
52.5 7.1 0.8 9.7 14/14 145/145 15
048-63
49.5 7.4 0.8 10.1 14/14 145/145 15
060-62
66.5 8.5 0.8 11.4 14/14 130/130 15
060-63
62.0 9.6 0.8 12.8 14/14 130/130 20