40MBAB: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
INSTALLATION REQUIREMENTS
Review the following information before installing the unit:
Do not install the indoor units near a direct source of heat such as
direct sunlight or a heating appliance.
Allow sufficient space for airflow and unit servicing. See Fig. 8 — on
page 6 for the minimum required distances between the unit and the
walls or ceilings.
Communication wiring must be at least 3 ft. (1m) away from all
electromagnetic interference (televisions, radios, etc.) sources.
Interference is still possible even if this distance is maintained.
Ensure any hanger used is strong enough to withstand the unit’s
weight.
If the indoor unit is installed in an unconditioned space, running for
long periods of time when the temperatures are outside the
recommended indoor unit operation ranges, it is recommended that the
installer seal all corners of the indoor unit to prevent any leaks and add
insulation material (13/32 to 13/16 in (10-20 mm)) to the entire surface
of the indoor unit to avoid condensation or heat transfer.
NOTE: Nuisance sweating may occur if the unit is installed in a high
humidity environment with low airflow.
Table 5 — Operating Range
NOTE: DO NOT install the indoor or outdoor units in a location with
special environmental conditions. For those applications,
contact your Ductless representative.
INSTALLATION
Step 1 - Check Equipment
Unpack the unit and move to the final location. Remove the carton, taking
care not to damage the unit. Inspect the equipment for damage prior to
installation. File a claim with the shipping company if the shipment is
damaged or incomplete. Locate the unit rating plate, which contains the
proper installation information. Check the rating plate to be sure the unit
matches the job specifications.
The indoor unit should be installed in a location that meets the following
requirements:
Enough room for installation and maintenance
Enough room for the lineset and drainpipe
A structure that can sustain the weight of the indoor unit
The air inlet and outlet are not impeded
There is no direct radiation from heaters
OPERATING RANGE (Min/Max °F (°C))
Cooling Heating
Indoor DB 62 / 90 (17 / 32) 32 / 86 (0 / 30)
Indoor WB 59 / 84 (15 / 29) N/A
Securely install the indoor unit on a structure that can sustain its
weight. If the structure is too weak, the unit may fall and cause
personal injury, unit and property damage, or death.
DO NOT install the indoor unit in a bathroom or laundry room as
excessive moisture can short the unit and corrode the wiring.
WAR N I N G
Install the indoor and outdoor units, cables and wires at least 3.2 ft
(1m) from televisions, routers, computer equipment or radios to
prevent static or image distortion. Depending on the appliances, a
3.2 ft (1m) distance may not be sufficient.
If the indoor unit is installed on metal, it must be electrically
grounded.
CAUTION
DO NOT install the unit in the following locations:
Areas with oil drilling or fracking
Coastal areas with high salt content in the air
Areas with caustic gases in the air, such as near hot springs
Areas with power fluctuations, such as factories
Enclosed spaces, such as cabinets
Areas with strong electromagnetic waves
Areas that store flammable materials or gas
Rooms with high humidity, such as bathrooms or laundry
rooms.
CAUTION