16
ELECTRICAL DATA
Table 6—Electrical Data
UNIT
SIZE
OPER. VOLTAGE
MAX / MIN*
COMPRESSOR OUTDOOR FAN INDOOR FAN
MCA
MAX FUSE
CB AMP
V/PH/HZ RLA V/PH/HZ FLA HP W V/PH/HZ FLA HP W
9K
253 / 187 208--- 230/1/60
5.3
208--- 230/1/60
0.42 0.053 40
208--- 230/1/60 0.146 0.061 46
15 15
12K 5.7 0.42 0.053 40 15 15
18K 7.3 0.85 0.067 50 13 20
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
F L A --- F u l l L o a d A m p s
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
CONNECTION DIAGRAMS
A150634
Fig. 36 --- Connection Diagrams
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
A150635
Fig. 37 --- Control and Power Wiring on Indoor Unit
NOTE: For applications where gravity cannot be used for drainage, a condensate pump accessory is available. Consult the
condensate pump installation instructions for more information.