– 21 –
Evaporator
Indoor unit
Cross flow fan
Cooling
Condenser
Propeller fan
Outdoor unit
Cooling
O.D.:15.88 mm O.D.:6.35 mm
Cooling
Gas container connection (Reinstall etc.)
Packed valve
(
∅
6.35)
Packed valve
(
∅
15.88)
0.39 m
(Connecting pipe)
∅
15.88
0.49 m
(Connecting pipe)
∅
6.35
T
P
Refrigerant
R22 1.70 kg
Mark ( ) means check points of Gas Leak
Capillary tube
∅2.4 x 1500 s
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.5 12.0 High 32/23 43/26*
Low temperature 0.3 1.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure
P
(MPaG)
5. REFRIGERATION CYCLE DIAGRAM
5-1. 42CJR024-723 / 38CJR024-723, 42TAR024X-723 / 38TAR024X-723
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
FILE NO. SVM-05010
Dryer
Compressor
PH400X3CS-4KT1