Install the outdoor unit on a rigid base to prevent increasing noise level and vibration.
Determine the air outlet direction where the discharged air is not blocked.
In the case that the installation place is exposed to strong wind such as a seaside operation by
putting the unit lengthwise along the wall or using a dust or shield plates.
Specially in windy area, install the unit to prevent the admission of wind. The connection betw-
een bracket and wall, bracket and the air conditioner should be firm, stable and reliable.
If need suspending installation, the installation bracket should accord with technique requir-
ement in the installation bracket diagram.
Strong
wind
.
.
.
.
1. OUTDOOR INSTALLATION PRECAUTION
Mod.
A mm
38YE009/012
B mm
C mm
D mm
E mm
F mm
A
B
C
D
E
A
F
100mm or more
100mm or more
600mm or more
1000mm or more
600mm or more
100mm or more
Fit the seal into the drain elbow,
then insert the drain elbow into
the base pan hole of outdoor unit,
rotate 90 to securely assemble
them. Connecting the drain elbow
with an extension drain hose
(Locally purchased), in case of the
water draining off the outdoor unit
during the heating mode.
2. DRAIN ELBOW INSTALLATION
Seal
Seal
Drain elbow
Drain elbow
Base pan hole of
outdoor unit
Base pan of
outdoor unit
42HQE009(012)/38YE009(012)
OURDOOR UNIT INSTALLATION
2
GB-8