86
System Heating Performance Data (Cont.)
Ducted Split System
53QDMT48-518 Heat Pump
380-420V/3Ph/50Hz
Indoor Conditions Outdoor Ambient Temperature
ESP
in.wg
Fan
Speed
Air
Flow
cfm
Temp. °C
DB
24/18°C DB/WB 7/6°C DB/WB 2/1°C DB/WB
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
0.36
in.wg
High
1043
15°C
54730 3910 44205 3370 36210 2900
20°C 53040 4265 42100 3615 34105 3185
27°C 49670 4530 39570 3915 32000 3450
Medium 933
15°C
51995 3755 41995 3240 34400 2785
20°C 50390 4095 39995 3475 32400 3060
27°C 47190 4350 37595 3760 30400 3315
Low 263
15°C
47315 3455 38220 2980 31305 2565
20°C 45855 3770 36400 3195 29485 2815
27°C 42940 4005 34210 3460 27665 3050
0.40
in.wg
High
1007
15°C
53950 3890 43575 3350 35690 2885
20°C 52285 4240 41500 3590 33620 3165
27°C 48960 4505 39005 3890 31540 3430
Medium 897
15°C
51255 3735 41400 3220 33910 2770
20°C 49675 4075 39425 3450 31940 3040
27°C 46515 4325 37055 3735 29965 3295
Low 206
15°C
46640 3440 37675 2960 30855 2550
20°C 45205 3745 35880 3175 29065 2800
27°C 42330 3980 33720 3440 27270 3030
42QDMT48-718