Carrier 42NQV050M - REFRIGERANT CYCLE DIAGRAM; Refrigerant Cycle Diagram

Carrier 42NQV050M
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
Max. : 20m
Deoxidized copper pipe
Outer dia. : 12.7mm
Thickness : 0.8mm
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating
valve at liquid side
(CAM-B22YGTF-3)
TD
4-way valve
(STF-0108Z)
Compressor
DA130A1F-27F
Propeller fan
Refrigerant amount : 1.40kg
OUTDOOR UNIT
Muffler
TC
TA
Min. : 2m
Chargeless : 15m
Charge : 20g/m
(16 to 20m)
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
2 - Dia 1.2 x 80
Outdoor heat
exchanger
Split capillary
TE
Muffler
Accumulater
tank
7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
TS
TO
DISTRIBUTOR
FILE NO. SVM-10052
42NQV050M / 38NYV050M2
42NQV050M-N / 38NYV050M2
42NQV050M-A / 38NYV050M-A
NOTE :
The maximum pipe length of this air conditioner is 20 m. When the pipe length exceeds 15m, the additional

Related product manuals