In  addition  to  conventional  charging  procedures, 
the following requirements shall be followed: 
Ensure  that  contamination  of  different 
refrigerants  does  not  occur  when  using  charging 
equipment.  Hoses  or  lines  shall  be  as  short  as 
possible  to  minimize  the  amount  of  refrigerant 
contained in them. 
Cylinders shall be kept upright. 
Ensure that the refrigeration system is earthed 
prior to charging the system with    refrigerant. 
Label the system when charging is complete (if 
not already). 
Extreme care shall be taken not to overfill the 
refrigeration system. 
Prior  to  recharging  the  system  it  shall  be 
pressure tested with OFN. The system shall be   
leak tested on completion of charging but prior to 
commissioning.  A  follow  up  leak  test  shall  be 
carried out prior to leaving the site. 
17. Decommissioning 
Before  carrying  out  this  procedure,  it  is  essential 
that  the technician  is  completely familiar  with  the 
equipment  and  all  its  detail.  It  is  recommended 
good  practice  that  all  refrigerants  are  recovered 
safely. Prior to the task being carried out, an oil and 
refrigerant sample shall be taken. 
In  case  analysis  is  required  prior  to  re-use  of 
reclaimed refrigerant. It is essential that   
electrical  power  is  available  before  the  task  is 
commenced. 
a)  Become  familiar  with  the  equipment  and  its 
operation. 
b) Isolate system electrically. 
c) Before attempting the procedure ensure that: 
mechanical  handling  equipment  is  available,  if 
required, for handling refrigerant cylinders; 
all  personal  protective  equipment  is  available 
and being used correctly; 
the recovery process is supervised at all times 
by a competent person; 
recovery  equipment  and  cylinders  conform  to 
the appropriate standards. 
d) Pump down refrigerant system, if possible. 
e) If a vacuum is not possible, make a manifold so 
that refrigerant can be removed from various parts 
of the system. 
f) Make sure that cylinder is situated on the scales 
before recovery takes place. 
g)  Start  the  recovery  machine  and  operate  in 
accordance with manufacturer's instructions. 
h)  Do  not overfill  cylinders.  (No  more  than  80  % 
volume liquid charge). 
i) Do not exceed the maximum working pressure of 
the cylinder, even temporarily. 
j) When the cylinders have been filled correctly and 
the  process  completed,  make  sure  that    the 
cylinders and the equipment are removed from site 
promptly and all isolation valves on the equipment 
are closed off. 
k) Recovered refrigerant shall not be charged into 
another refrigeration system unless it has   
been cleaned and checked. 
18. Labelling 
Equipment shall be labelled stating that it has been 
de-commissioned and emptied of   
refrigerant.  The  label  shall  be  dated  and  signed. 
Ensure  that  there  are  labels  on  the  equipment 
stating  the  equipment  contains  flammable 
refrigerant. 
19. Recovery 
When removing refrigerant from a system, either 
for servicing or decommissioning, it is   
recommended good practice that all refrigerants are 
removed safely. 
When  transferring  refrigerant  into  cylinders, 
ensure that only appropriate refrigerant   
recovery cylinders  are  employed. Ensure that the 
correct  numbers  of  cylinders  for  holding  the  total 
system  charge  are  available.  All  cylinders  to  be 
used are  designated for the recovered refrigerant 
and  labelled  for  that  refrigerant  (i.e.  special 
cylinders for the recovery of refrigerant). Cylinders 
shall  be  complete  with  pressure  relief  valve  and 
associated shut-off valves in good working order.   
Empty recovery cylinders are evacuated and, if 
possible, cooled before recovery occurs. 
The  recovery  equipment  shall  be  in  good 
working order with a set of instructions concerning 
the equipment that is at hand and shall be suitable 
for  the  recovery  of  flammable  refrigerants.  In 
addition, a set of calibrated weighing scales shall 
be available and in good working order. 
Hoses  shall  be  complete  with  leak-free 
disconnect couplings and in good condition. Before 
using  the  recovery  machine,  check  that  it  is  in 
satisfactory  working  order,  has  been  properly 
maintained  and  that  any  associated  electrical 
components are sealed to prevent   
ignition in the event of a refrigerant release. Consult 
manufacturer if in doubt. 
The  recovered  refrigerant  shall  be  returned  to 
the refrigerant supplier in the correct   
recovery cylinder, and the relevant Waste Transfer 
Note arranged. Do not mix refrigerants   
in recovery units and especially not in cylinders. 
If  compressors  or  compressor  oils  are  to  be 
removed, ensure that they have been   
evacuated to an acceptable level to make certain 
that flammable refrigerant does not