29
APPENDIX A -- USER INTERFACE MENUS (CON’T)
Status Menus
BACview MENU POINT NAME BACnet OBJECT RANGE
FIELD ASSISTANT
MENU
HOME Select function below Properties/Equipment
STA TUS STATUS Status
System Mode mode_status
1=Disabled
2=Test
3=Run
Operating Mode run_status
1=Off
2=Fan Only
3=Economizer
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdown
9=Unocc Free Cooling (NT-
FC)
Supply Fan Status sfan_status O ff/Running
Space Temperature --- Prime Vari-
able
space_temp xxx ° F
Supply Air Temperature sa_temp xxx ° F
Outdoor Air Temperature oa_temp xxx ° F
Space Relative Humidity space_rh 0 --- 1 0 0 %
Indoor Air CO2 iaq 0---5000 ppm
Outdoor Air CO2 oaq 0---5000 ppm
Economizer Output econ_output 0 --- 1 0 0 % o p e n
LINKAGE AIR LINKAGE Linkage
Airside Linkage Status a_link_status Not Active/Active
Number of Providers link_collector/4602 xx
Occupancy Status link_occ Unoccupied/Occupied
Space Temperature link_spt xxx ° F
Occupied Cooling Setpoint link_occ_cl_stpt 55---80 ° F
Occupied Heating Setpoint link_occ_ht_stpt 55 --- 80 ° F
Unoccupied Cooling Setpoint link_unocc_cl_stpt 75---130 ° F
Unoccupied Heating Setpoint link_unocc_ht_stpt 55--- 85 ° F
Indoor Air CO2 (ppm) link_iaq xxxx ppm
Space Relative Humidity link_sprh xxx %