APPENDIX A -- USER INTERFACE MENUS (CON’T)
Configuration Menus
BACview MENU POINT NAME
BACnet
OBJECT
RANGE DEFAULT FIELD ASSISTANT MENU
HOME Select function below Properties/Equipment
CONFIG CONFIGURATION Configuration
SETPOINT
SETPOINTS
Setpoints
Occupied Heating Setpoint occ_ht_stpt 40---90 ° F 70
Occupied C ooling Setpoint occ_cl_stpt 55 ---99 ° F 74
Unoccupied Heating Setpoint unocc_ht_stpt 40---90 ° F 55
Unoccupied Cooling Setpoint unocc_cl_stpt 55 ---99 ° F 90
Effective Cool Setpoint eff_cl_stpt xx ° F
Effective Heat Setpoint eff_ht_stpt xx ° F
Optimal Start optm_start 0 --- 4 h r 4
Occ Relative Humidity Setpoint occ_dehum_stpt 0 --- u n o c c se t -
point %rh
60
Unocc Relative Humidity Set-
point
unocc_de-
hum_stpt
30---100 %rh 95
DCV Max Ctrl Setpoint iaq_stpt_max 0---9999 ppm 650
Power Exhaust Setpoint pexh_stpt 20 ---90 %Open 50
Sched
Weekly schedule M O N --- S U N none
(BACview Only)
Exceptions none
ALARMS
ALARM CONFIGURATION
Alarm Configuration
SP ACE TEMPERATURE ALARM
Occupied Alarm Hysteresis occ_spt_alrm_hys
t
2 --- 2 0 ° F 3
Alarm Delay (min/deg) spt_alrm_delay 0 --- 3 0 m i n u t e s 10
Unoccupied Low SPT Alarm
Limit
uno_spt_alrm_lo_l
mt
35---90 ° F 45
Unoccupied High SPT Alarm
Limit
uno_spt_alrm_hi_l
mt
45---100 ° F 95
SUPPLY AIR TEMPERA TURE ALARM
Low SAT Alarm Limit sat_lo_alrm_lim 15---90 ° F 35
High SAT Alarm Limit sat_hi_alrm_lim 90 ---175 ° F 160
SP ACE HUMIDITY ALARM
Low Space Humidity Alarm
Limit
sprh_lo_alrm_lim 0 --- 9 9 % r h 30
High Space Humidity Alarm
Limit
sprh_hi_alrm_lim 0 --- 9 9 % r h 70
IAQ / VENTILATION ALARM
Occ High CO2 Alarm Limit
(ppm)
iaq_occ_hi_lmt 0 ---9999 ppm 1200