44
CONFIGURATION POINTS (CON’T)
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE DEFAULT ENTRY
HOME Select function below
CONFIG CONFIGURATION
SERVICE
SERVICE CON FIGURATION
Unit Type unit_type 1=Heat/Cool
2=HP O/B Ctrl
3=HP Y1/W1 Ctrl
Heat/Cool (TC and HC
models)
HP Y1/W1 Ctrl (TCQ
and HCQ models)
Compressor Stages comp_stages One stage/ Two
Stage
One Stage (sizes
04---07, and A08--- A12)
Two Stages (sizes
08---30)
Economizer Exists econ_exist No/Yes No (No FIOP)
Yes (FIO P)
Reversing Valve Ty pe rev_vlv_type Ooutputtype/B
output type
Ooutputtype
Heat Type heat_type Electric/Gas Gas (48 Series Units)
Electric (50 Series
Units)
Number of Heat Stages heat_stages 1/2/0(noheat) 0 (50 series cooling
only units)
1(AllTCQsandHCQs,
Low Nox units, single
phase gas units,
TC04--- 09 low and
TC05--- 07 med heat 3
phase gas units)
2 (TC04 and 08--- 09
med, TC05---09 high
heat 3 p hase gas units,
H C 0 4 --- 0 9 3 p h a s e g a s
units and All 12---30
gas units)
Continuous Occupied Exhaust occ_exh No/Yes No
Indoor CO2 Sensor Value @ Min mA iaq_ref_lo_ppm 0--- 9999ppm 0
Indoor CO2 Sensor Value @ Max mA iaq_ref_hi_ppm 0---9999ppm 2000
Outdoor CO2 Sensor Value @ Min
mA
oaq_ref_lo_ppm 0--- 9999ppm 0
Outdoor CO2 Sensor Value @ Max
mA
oaq_ref_hi_ppm 0--- 9999ppm 2000