APPENDIX A - LOCAL DISPLAY AND CCN TABLES
Table 27 MODE - RUN STATUS
ITEM EXPANSION RANGE UNITS
CCN
TABLE/SUB--- TABLE
CCN POINT
CCN WRITE
STATUS
RUN STATUS STATUS DISPLAY
VIEW Auto View of Run Status (VIEW = Display only)
HVAC HVAC Mode Status 1=Disabled
2=Fan Only
3=Cool
4=Heat
HVACMODE
OCC Currently Occupied Yes/No OCCUPIED
SAT Supply Air Temperature xxx..x dF SAT_DISP
ALRM Current Alarms & Alerts xx ALRMALRT
TIME Time of Day xx.xx hh.mm TIMECOPY
VERS Software Version Numbers VERSIONS
MBB CESR131459--- xx--- xx ( x x --- x x i n
table)
MODEL_NUMBER_01
ECB CESR131249--- xx--- xx MODEL_NUMBER_02
AUX CESR131333--- xx--- xx MODEL_NUMBER_03
MARQ CESR131171--- xx--- xx MODEL_NUMBER_04
MODE Control Modes MODEDISP
SYS Unit operation disabled
Unit operation enabled
Service test enabled
SYS_MODE_TEXT1
SYS_MODE_TEXT2
(table only)
SYS_MODE_TEXT3
(table only)
HVAC HVAC Operation Disabled
Ventilation (fan--- only)
Cooling
Unoccupied Free Cooling
Heating
HVACMODE_TEXT_1
HVACMODE_TEXT_2
(table only)
HVACMODE_TEXT_3
(table only)
HV.DN Remote HVAC Mode Disable Yes/No HVACDOWN forcible
EFF.C Cool Setpoint in Effect xxx.x CSP_EFF
EFF.H Heat Setpoint in Effect xxx.x HSP_EFF
OCC Currently Occupied Yes/No OCCUPIED forcible
T. O V R Timed Override in Effect Yes/No MODETOVR
LINK Linkage Active Yes/No MODELINK
D.LMT Demand Limit In Effect Yes/No MODEDMDL
C.LOC Compressor OAT Lockout Yes/No COMPLOCK
H.LOC Heat OAT Lockout Yes/No HEATLOCK
E.LOC Econo Cool OAT Lockout Yes/No ECONLOCK
COOL Cooling Status COOLDISP
DMD.C Cooling Demand xxx.x ^F COOL_DMD
SA.CP Supply Air Control Point xxx.x dF SA_CTLPT
SASP Cool Supply Air Setpoint xxx.x dF SASP
SR.CD Cool Demand SASP Reset xxx.x ^F CD_RESET
SR.RH Dehumidifying SASP Reset xxx.x ^F RH_RESET
F.SPD Commanded Fan Speed xxx % FANSPEED
CMP.A Compressor A Feedback On/Off COMP_A
TG.A Compressor A Timeguard xxx sec TIMGD_A
CAPC Compressor Capacity xxx % CAPACITY
MAX.C Max Compressor Capacity xxx % MAX_CAPC forcible
MIN.C Min Compressor Capacity xxx % MIN_CAPC
LMT.C Max Capacity In Effect xxx % CAPLIMIT
SST.A Sat. Suction Temp A xxx.x dF SST_A
SSP.A Suction Pressure A xxx.x psig SSP_A
SCT.A Sat. Condenser Temp A xxx.x dF SCT_A
SCP.A Condenser Pressure A xxx.x psig SCP_A
OFC.1 Outdoor Fan 1 Relay On/Off OFC_1
HEAT Heating Status HEATDISP
DMD.H Heating Demand xxx.x ^F HEAT_DMD
AVL.H Available Heating Stages x AVLHSTGS
REQ.H Requested Heating Stages x REQHSTGS
MAX.H Max Allowed Heat Stages x MAXHSTGS forcible
LMT.H Max Heat Stage In Effect x HSTGLIMT
F.SPD Commanded Fan Speed xxx % FANSPEED
HT.1 Heat Stage 1 Relay On/Off HEAT_1
TG.H1 Heat Stage 1 Timequard xxx sec TIMGD_H1
HT.2 Heat Stage 2 Relay On/Off HEAT_2
TG.H2 Heat Stage 2 Timequard xxx sec TIMGD_H2
ECON Economizer Status ECONDISP
EC.CP Econo Commanded Position xxx % ECONOCMD
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP MinPositioninEffect xxx % MIN_POS
IAQ.S IAQ Level (switch) High/Low IAQIN
IAQ IAQ Level (sensor) xxxx ppm IAQ
OAT Outdoor Air Temperature xxx.x dF OA_TEMP
ENTH Outdoor Enthalpy Switch High/Low ENTHALPY
OAQ OAQ Level (sensor) xxxx ppm OAQ
PE.1 Power Exhaust 1 Relay On/Off PE_1
PE.2 Power Exhaust 2 Relay On/Off PE_2
HRS Component Run Hours STRTHOUR
A1 Compressor A1 Run Hours xxxxx.xx hours HR_A1 forcible
CCH Crankcase Htr Run Hours xxxxx.xx hours HR_CCH forcible
IDF Indoor Fan Run Hours xxxxx.xx hours HR_IDF forcible
OFC.1 Outdoor Fan 1 Run Hours xxxxx.xx hours HR_OFC_1 forcible
HT.1 Heat Stage 1 Run Hours xxxxx.xx hours HR_HTR_1 forcible
HT.2 Heat Stage 2 Run Hours xxxxx.xx hours HR_HTR_2 forcible
PE.1 Power Exhaust1 Run Hours xxxxx.xx hours HR_PE_1 forcible
PE.2 Power Exhaust2 Run Hours xxxxx.xx hours HR_PE_2 forcible
ALRM Alarm Relay Run Hours xxxxx.xx hours HR_ALM forcible