Accessory/FIOP Pressure Drop (in. wg) 48/50PG03-07
AIRFLOW
(CFM)
ELECTRIC
HEAT
(Sizes 03‐07)
ECONOMIZER
(Vertical)
(Sizes 03‐07)
ECONOMIZER
(Horizontal)
(Sizes 03‐07)
Humidi-MiZer™
SYSTEM
(Sizes 03‐04)
Humidi-MiZer™
SYSTEM
(Sizes 05‐07)
600
0.01 0.01 0.03 0.01
800
0.01 0.01 0.05 0.02
1000
0.02 0.02 0.07 0.03
1200
0.02 0.03 0.10 0.04 0.02
1400
0.03 0.04 0.14 0.04 0.03
1600
0.04 0.06 0.17 0.05 0.03
1800
0.05 0.07 0.22 0.04
2000
0.07 0.09 0.26 0.04
2200
0.08 0.11 0.31 0.05
2400
0.10 0.13 0.37 0.06
2600
0.11 0.15 0.43 0.06
2800
0.13 0.18 0.49 0.07
3000
0.15 0.21 0.56 0.08
Accessory/FIOP Pressure Drop (in. wg) 48/50PG08-14
AIRFLOW
(CFM)
ELECTRIC
HEAT
ECONOMIZER
(Vertical)
ECONOMIZER
(Horizontal)
Humidi-MiZer
SYSTEM
2250
0.03 0.05 0.10 0.03
2650
0.05 0.06 0.13 0.03
3050
0.06 0.08 0.17 0.04
3450
0.08 0.09 0.21 0.05
3850
0.10 0.10 0.26 0.06
4250
0.12 0.12 0.31 0.07
4650
0.14 0.13 0.37 0.08
5050
0.17 0.15 0.44 0.09
5450
0.20 0.17 0.50 0.10
5850
0.23 0.18 0.58 0.11
6250
0.26 0.20 0.66 0.12
LEGEND
FIOP - Factory-Installed Option
* The static pressure must be added to the external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the
Fan Performance tables to determine blower rpm and watts.