MODE CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE NO.
OAU Outside Air Unit Config OAU_CFG 12
OA.TY Outdoor Air Unit Type 0=No OAU
1=ERV Module
2=Economizer
3=Pwr Exhaust
4=OA Monitor
5=100% OA
Unit
6=EXv1 ERV
0: no FIOP
1: FIOP EXv2
OAU_TYPE 40
OA.FC Outside Air Fan Curve 0 to 999 0: no FIOP
1: PG0307 1ph low
CFM ERV
2: PG0307 3ph low
CFM ERV
3: PG0307 1ph high
CFM ERV
4: PG0307 3ph high
CFM ERV
5: PG0814 low CFM
ERV
6: PG0814 high CFM
ERV
7: PM1624 low CFM
ERV
8: PM1624 high CFM
ERV
9: PM28 low CFM ERV
10: PM28 high CFM
ERV
OAFANCRV 105
PE.FC Exhaust Air Fan Curve 0 to 999 0: no FIOP
1: PG0306 1ph low
CFM ERV
2: PG0307 3ph low
CFM ERV
3: PG0306 1ph high
CFM ERV
4: PG0307 3ph high
CFM ERV
5: PG0814 low CFM
ERV
6: PG0814 high CFM
ERV
7: PM1624 low CFM
ERV
8: PM1624 high CFM
ERV
9: PM28 low CFM
ERV
10: PM28 high CFM
ERV
PEFANCRV 105
U.RUN OAU Unoccupied Operation No/Yes NO UNOCCRUN 105
OAU.F Shut Down on Fan Failure No/Yes Yes FATALOAU 105
M.WHL Modulating Wheel Install No/Yes NO MODWHEEL 105
OA.MN Minimum Outside Air
CFM
0 to 32000 CFM 375: PG0307 low
CFM ERV
800: PG0307 high
CFM ERV
1000: PG0814 low
CFM ERV
2500: PG0814 high
CFM ERV
3000: PM1628 low
CFM ERV
4000: PM1624 high
CFM ERV
5000: PM28 high
CFM ERV
MINOACFM 95
DCV.M Min DCV Outside Air CFM 0 to 32000 CFM 100: PG0307 ERV
250: PG0814 low
CFM ERV
600: PG0814 high
CFM ERV
1000: PM1624 low
CFM ERV
1500: PM1624 high
CFM ERV, PM28 low
CFM ERV
2000: PM28 high
CFM ERV
MINDCVSP 95
PEX.C Power Exhaust Control 0=Offset CFM
1=BP
0 PEX_CTL 105
PE.OF Power Exhaust CFM Offset 17000 to
17000
CFM 200 EXOFFSET 95
BP.SP Building Pressure Setpnt 0.25 to 0.25 in H2O 0.05 OAU_BPSP 95
OA.TM Outside Air Tempering Disable/Enable Disable OATEMPER 95
TM.LO OA Tempring Lockout Temp 0 to 80 °F 60 OATMPLOC 95
TM.SP OA Tempring SAT Setpoint 35 to 80 °F 55 OATMPSPT 95
OAC.K Outside Air CFM k Factor 0.8 to 1.2 1.0 OACFM_K 105
EXC.K Exhaust Air CFM k Factor 0.8 to 1.2 1.0 EXCFM_K 105