APPENDIX A — LOCAL DISPLAY AND CCN TABLES
MODE — RUN STATUS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S U B --- T A B L E
CCN POINT
CCN WRITE
STATUS
RUN STA TUS STATUS DISPLA Y
VIEW Auto View of Run Status (VIEW = Display only)
HVAC HVAC Mode Status 1=Disabled
2=Ventilation
3=Cool
4=Heat
HVACMODE
OCC Currently Occupied Yes/No OCCUPIED
SAT Supply Air Temperature xxx..x dF SAT_DISP
ALRM Current Alarms & Alerts xx ALRMALRT
TIME Time of Day xx.xx hh.mm TIMECOPY
VERS Software Version Numbers VERSIONS
MBB CESR131320--- xx--- xx
( x x --- x x i n
table)
MODEL_NUMBER_01
ECB CESR131249--- xx--- xx MODEL_NUMBER_02
MARQ CESR131171--- xx--- xx MODEL_NUMBER_03
MODE Control Modes MODEDISP
SYS Unit operation disabled
Unit operation enabled
Service test enabled
1of3textwill
be displayed
SYS_MODE_TEXT1
SYS_MODE_TEXT2
(table only)
SYS_MODE_TEXT3
(table only)
HVAC HVAC Operation Disabled
Ventilation (fan--- only)
Cooling
Free Cooling
Unoccupied Free Cooling
Reheat1
Reheat2
Reheat1 / Reheat 2
Heating
1of9textwill
be displayed
HVACMODE_TEXT_1
HVACMODE_TEXT_2
(table only)
HVACMODE_TEXT_3
(table only)
HV.DN Remote HVAC Mode Disable Yes/No HVACDOWN forcible
EFF.C Cool Setpoint In Effect xx.x dF CSP_EFF
EFF.H Heat Setpoint in Effect xx.x dF HSP_EFF
OCC Currently Occupied Yes/No OCCUPIED forcible
T. OV R Timed Override in Effect Yes/No MODETOVR
LINK Linkage Active Yes/No MODELINK
D.LMT Demand Limit In Effect Yes/No MODEDMDL
C.LOC Compressor OAT Lockout Yes/No COMPL OCK
H.LOC Heat OAT Lockout Yes/No HEATLOCK
E.LOC Econo Cool OAT Lockout Yes/No ECONLOCK
COOL Cooling Status COOLDISP
DMD.C Cooling Demand xxx.x ^F COOL_DMD
AVL.C Available Compressors x AVLCSTGS
REQ.C Requested Compressors x REQC STGS
MAX.C Max Allowed Cool Stages x MAXCSTGS forcible
LMT.C Max Cool Stage In Effect x CSTGLIMT
IDF Indoor Fan State On/Off IDFSTATE
F.SPD Commanded Fan Speed xxx FANSPEED
OFC.1 Outdoor Fan 1 Relay On/Off OFC_1
OFC.2 Outdoor Fan 2 Relay On/Off OFC_2
OFC.3 Outdoor Fan 3 Relay On/Off OFC_3
CRC Cool--- >Reheat1 Control On/Off CRC
CIR.A Refrigerant Circuit A
CMP.A Compressors A On/Off COMP_A
TG.A Timeguard A xxx sec TIMGD_A
RH2.A Reheat2 Valve A On/Off RH 2_A
SST.A Sat. Suction Temp A xxx.x dF SST_A
SSP.A Suction Pressure A xxx.x psig SSP_A
SCT.A Sat. Condenser Temp A xxx.x dF SCT_A
SCP.A Condenser Pressure A xxx.x psig SCP_A
CIR.B Refrigerant Circuit B
CMP.B Compressors B On/Off COMP_B
TG.B Timeguard B xxx sec TIMGD_B
RH2.B Reheat2 Valve B,C On/Off RH2_B
SST.B Sat. Suction Temp B xxx.x dF SST_B
SSP.B Suction Pressure B xxx.x psig SSP_B
SCT.B Sat. Condenser Temp B xxx.x dF SCT_B
SCP.B Condenser Pressure B xxx.x psig SCP_B
CIR.C Refrigerant Circuit C
CMP.C Compressors C On/Off COMP_C
TG.C Timeguard C xxx sec TIMGD_C
RH2.C Reheat2 Valve B,C On/Off RH2_B
SST.C Sat. Suction Temp C xxx.x dF SST_C
SSP.C Suction Pressure C xxx.x psig SSP_C
SCT.C Sat. Condenser Temp C xxx.x dF SCT_C
SCP.C Condenser Pressure C xxx.x psig SCP_C